346 Appendix
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
750-494, -495, (and all variations)
The 3-Phase Power Measurement Modules 750-494, -495, (and all variations)
have a total of 24 bytes of user data in both the Input and Output Process Image
(16 bytes of data and 8 bytes of control/status).
Table 254: 3-Phase Power Measurement Modules 750-494, -495, (and all variations)
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
S1
S0
Status word
1
S3
S2
Extended status word 1
2
S5
S4
Extended status word 2
3
S7
S6
Extended status word 3
4
D1
D0
Process value 1
5
D3
D2
6
D5
D4
Process value 2
7
D7
D6
8
D9
D8
Process value 3
9
D11
D10
10
D13
D12
Process value 4
11
D15
D14
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
S1
S0
Control word
1
S3
S2
Extended control word 1
2
S5
S4
Extended control word 2
3
S7
S6
Extended control word 3
4
-
-
-
5
-
-
6
-
-
-
7
-
-
8
-
-
-
9
-
-
10
-
-
-
11
-
-