260 CANopen Master and Slave
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
Table 193: Description of the CAN Parameters (Slave)
Parameters
Explanation
Heartbeat Settings
Activate heartbeat
generation
If the “Heartbeat Generation” option is enabled, the
CAN device transmits heartbeats in ms intervals
specified in “Heartbeat Producer Time”.
This function is disabled by “0”.
Heartbeat producer time
(ms)
Activate heartbeat
consumption
If the “Heartbeat Consumption” option is enabled,
the CAN device monitors the heartbeat of the
master. Only “Heartbeat” or “Node-Guarding” can be
used for monitoring.
Emergency Telegram
Emergency
If you mark this checkbox, the slave sends error and
status messages that are stored as emergency
messages to the diagnostic address in the flag area.
These error and status messages are read out using
“BusDiag.lib”.
If you do not mark this checkbox, SDO 0x1014 is not
transmitted to the slave. The default setting for the
slave would then still apply.
COB-ID
Default: Node ID + 0x80
Communication Cycle
Cycle
These functions are currently not implemented.
Period (µsec)
Click
[Info …]
to display the parameters “FileInfo” and “DeviceInfo” from the EDS
file.