WAGO-I/O-SYSTEM 750
Device Description
49
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
3.8.8
CANopen
Table 21: Technical Data
– CANopen
CANopen input and output process
image max.
2000 words
No direct access from fieldbus to the process image for I/O modules!
Any data that is required from the I/O module process image must be explicitly
mapped in the CODESYS program to the data in the fieldbus process image and
vice versa! Direct access is not possible!
3.8.9
PROFINET IO
Table 22: Technical Data
– PROFINET
Interfaces
2 x RJ45 (X11, X12)
MRP
Client (X11, X12)
Reduction Ratio
4 … 512
PROFINET input and output process
image max.
1024 byte, 1 AR
No direct access from fieldbus to the process image for I/O modules!
Any data that is required from the I/O module process image must be explicitly
mapped in the CODESYS program to the data in the fieldbus process image and
vice versa! Direct access is not possible!
3.8.10
USB Service Interface
Table 23: Technical Data
– USB-Service Interface
Interface type
USB-A
Specification
USB 2.0
Current load capacity
500 mA
The USB service port should only be used for commissioning and service
purposes.
In normal operation, the port socket must be closed with the included stopper!
USB service port only for removable storage devices!
Only USB sticks should be connected to the USB service port.