Table 190: Description of the CAN Parameters (Master)
Parameters
Explanation
Support ... DSP 301
If you mark this check box, modular CAN slaves as
well as additional extensions adhering to the
DSP301 V3.01 and DSP 306 standards are
supported by the control configuration.
Heartbeat Master
If the “Heartbeat Generation” option is enabled, the
CAN device transmits heartbeats in ms intervals
specified in “Heartbeat Producer Time”. Heartbeat
consumption is not currently implemented.
In the “Module parameters” tab you can define the start and stop behavior of the
master.
Figure 54: Module Parameters Tab (Master)
Table 191: Description of the Module Parameters (Master)
Parameters
Explanation
Scan all node IDs on boot
All permissible node IDs are scanned at the start if
this option is set. EMC messages are received from
this node if a node is present.
Goto Preoperational on
PLC stop
If this option is set, the master switches to the
“Operational” state if the CODESYS runtime is in the
“Run” state.
If the runtime switches to the “Stop” state, the
master switches to the “Preoperational” state.
10.3.4.3 Adding Slaves
To select one (or several) CANopen slaves, right-click on the CANopen master
and select “Attach subelements”. In this example, the 750-337 was selected as
the slave.