Table 193: Description of the CAN Parameters (Slave)
Parameters
Explanation
General
Node ID
The node ID (1
–126) is the station address under
which the controller communicates with the slave on
the CAN network.
Write DCF
Currently not implemented.
Generate all SDOs
When this check box is marked, SDOs are
generated for all objects in the EDS file.
In addition, the corresponding options must be
activated. If the node-guarding objects are to be
written, for example, the checkbox for the “Node-
Guarding” option must also be marked.
If the checkbox is not marked, SDOs are only
generated for the objects in which the default values
deviate from the EDS file.
Reset node
If you activate this option, the slave is reset by the
controller (receives a “reset node”) before the
configuration is sent to the slave.
This function is not currently implemented.
Mapping SDOs
Activate or deactivate each of the three SDO ranges
of the slave configuration here.
Comm SDOs
Mapping SDOs:
Objects 0x1600 … 0x1620
Objects 0x1A00 … 0x1A20
Comm SDOs:
Objects 0x1400 … 0c1420
Objects 0x1800 … 0x1820
Basic SDOs:
Objects 0x1
00C … 0x1017
Basic SDOs
Node Guard
Node-Guarding
With Node-Guarding enabled, the slave monitors the
PFC for any potential disruption of fieldbus
communication.
Guard COB ID
Default setting: 0x700 + Node ID.
Guard Time (ms)
Under“Guard Time” specify the interval at which the
PFC expects to receive “Confirmation” from the
slave.
Lifetime factor
In the field “Lifetime factor” (>= 2) specify the
multiplier for the “Guard time”.
If the time yielded from “Guard time” x "Lifetime
factor” “Node lifetime”) has expired, the slave is
brought into the predefined state.
This function is deactivated by “0”.