284 CANopen Master and Slave
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
4.
Open the
Module parameters
tab of the slave. For communication with
simple CAN Layer2 devices, deactivate transmission of the configuration to
the slave with
EnableCANopenStartup
(= “No”).
Figure 81
: “Module Parameters” Tab
5.
Open the
CAN parameters
tab of the slave. Deactivate the parameters
CommSDO
,
MappingSDO
,
Basic SDO
and
Nodeguarding
.
Figure 82
: “CAN Parameters“ Tab
6.
You can now use the commands of the CAN Layer2 library (see Section
“CODESYS Libraries” > … > “WagoCANLayer2_01.lib”) to access the
devices.
To configure the CAN frames for CAN Layer2 devices, refer to the Section
“CANopen Master and Slaves” > … > “Configuring the slave PDOs”.