WAGO-I/O-SYSTEM 750
Modbus
– e!RUNTIME 227
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
9.2
Modbus Registers
Table 179: WAGO Modbus Registers
Modbus Address
Data Length
in Words
Access Description
Dec.
Hex.
Watchdog Configuration Registers
64,000
0xFA00
1
w
Watchdog command register
64,001
0xFA01
1
rw
Watchdog timeout register
64,002
0xFA02
1
ro
Watchdog status register
64,003
0xFA03
1
rw
Watchdog config register
64,004
0xFA04
1
rw
Modbus TCP connection
watchdog register
Status Registers
64,010
0xFA0A
1
ro
LED flash code I/O-LED
(sequence 1 of 3)
64,011
0xFA0B
1
ro
LED flash code I/O-LED
(sequence 2 of 3)
64,012
0xFA0C
1
ro
LED flash code I/O-LED
(sequence 3 of 3)
64,013
0xFA0D
1
ro
PLC State : 1 = Stop; 2 = Run
Electronic Type Label
64,016
0xFA10
4
ro
Order number, e.g.,
0750810100400001
64,020
0xFA14
1
ro
Firmware status
64,021
0xFA15
1
ro
Hardware version
64,022
0xFA16
1
ro
Firmware loader
Process Image Version
64,023
0xFA17
1
ro
Version of the Modbus process
image
Network Configuration
64,032
0xFA20
3
ro
MAC-ID 1
Process Image Registers
64,064
0xFA40
1
ro
Number of input registers, analog
and digital (total size of the
Modbus IN space) 0x7D00
64,065
0xFA41
1
ro
Number of input registers, analog
0x7D00
64,066
0xFA42
1
ro
Number of input registers, digital
0x8000
64,067
0xFA43
1
ro
Number of output registers,
analog and digital (total size of
the Modbus OUT space) 0x7D00
64,068
0xFA44
1
ro
Number of output registers,
analog 0x7D00
64,069
0xFA45
1
ro
Number of output registers,
digital 0x8000