WAGO-I/O-SYSTEM 750
Diagnostics 297
750-8215 PFC200; G2; 4ETH CAN USB
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
The BF LED indicates following diagnostics:
Table 208
: “BF” Diagnostics LED
Status
Explanation
Remedy
Green
PROFINET
communication
established
---
Green, flashing,
500 ms
PROFINET DCP
signal request
received;
Signaling duration: 3
seconds
---
Red
PROFINET
configured; no
PROFINET-compliant
link available.
Check the network connection to the
PROFINET IO Controller.
Red, flashing,
500 ms
PROFINET
configured; link
available; no
connection to the
PROFINET IO
Controller.
Check the network connection to the
PROFINET IO Controller.
Off
No PROFINET device
configuration was
created in
e!
COCKPIT
. No
PROFINET
communication
possible.
Check the device configuration in
e!
COCKPIT
or create the device
configuration.