5. Periodic test
D-307083 PowerMaster-360R Installer's Guide
63
Option
Instructions
To test the microwave range of the dual detector:
1.
Press
to enter the
TEST ONE DEVICE
sub menu and use
to navigate to
MOTION SENSORS
.
2.
Press
; the following screens will appear:
Z01:Motion Sens
<location>
.
3.
Press
continuously to select a different zone number.
4.
Press
; If the selected device is Tower-32AM PG2, the following screens will
appear:
<OK MW ADJUST>
<NEXT>
TEST ONE
.
To test the microwave range, go to step 5. To test a different microwave range, go to step 7.
5.
Press
; the following screen will appear:
ACTIVATE MW NOW
.
6.
Activate the device; the screen will return to
TEST ONE DEVICE
.
You can now repeat the procedure for another dual detector.
7.
Press
to select the sensitivity setting.
8.
Press
continuously to select between
Minimum
(default),
Medium
or
Maximum
9a
. Press
; the panel will receive an acknowledge from the device that is indicated by a
black box next to the selected setting. Thereafter, the screen momentarily changes to
ACTIVATE MW NOW
and then returns to the selected setting.
9b
. If you press
, the adjustment procedure ends.
Important
: The procedure mentioned above is for testing purposes only and does not
change the detector settings. The settings must be saved through the MODIFY DEVICES
menu.
To test the shock detector:
1.
Press
to enter the
TEST ONE DEVICE
sub menu and use
to navigate to
SHOCK SENSORS
.
2.
Press
; the following screens will appear:
Zxx:Shk+AX+CntG3
1
<location>
.
3.
Press
continuously to select a different zone number.
4.
Press
; the following screens will appear:
Zxx ACTIVATE NOW
SHOCK NOT
ACTIV
.
CNTACT NOT ACTIV
AUXIL. NOT ACTIV
.
Note:
The above screens are the full range of screens that can appear and indicate the
inputs that have not yet been activated. However, since there are various models of the
shock detector, not all of these screens will appear on some models.
5.
At this stage, activate each input of the shock detector in turn.
To test motion detector with integrated camera (Next CAM PG2 or TOWER CAM PG2):
1.
Press
to enter the
TEST ONE DEVICE
sub menu and use
to navigate to
MOTION SENSORS
.
2.
Press
; the following screens will appear:
Z01:Motion Sens
<location>
.
3.
Press
continuously to select a different zone number.
4.
Press
; the following screen will appear:
Zxx ACTIVATE NOW
.
5.
Activate the input of the detector; the following screens will appear:
<Zxx IS
ACTIVATE>
<OK>
SEND IMAGE
.
E-MAIL TEST
To test emails, proceed as follows:
While in
E-MAIL TEST
, press
to initiate the test.
The following screen will appear:
Please wait…
and at the termination of the test will
1
Depending on shock detector model, one of the following may appear instead:
Zxx:Shk+AX
/
Zxx:Shk+CntG3
/
Zxx:Shk+CntG2
.