![Visonic PowerMaster-360R Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/visonic/powermaster-360r/powermaster-360r_installers-manual_1032858038.webp)
4. Programming
38
D-307083 PowerMaster-360R Installer's Guide
Plink GPRS
The GSM/GPRS module is capable of communicating with the monitoring station
receiver by GPRS or SMS channels.
The GPRS channel is always enabled. If it fails, the GPRS module will try to
communicate via SMS.
Limited (default)
– Plink uses GPRS only when the wired Ethernet channel is not
functional, and for event and film reports (keep-alive and NTP mechanism will not use
the GPRS channel).
Unlimited
– Plink uses GPRS only when the wired Ethernet channel is not functional,
and for any other purpose.
Disable
– Plink does not use GPRS for event reports, film reports, or the home
automation app.
4.6.3 Configuring event reporting to monitoring stations
The PowerMaster-360R control panel is designed to report alarm, alerts, troubles and other events and messages to
two Monitoring Stations C.S.1 and C.S.2 via Cellular i.e. GPRS (IP) & SMS or Broadband IP communications channels.
In this section you configure and define all parameters and features required for the reporting of the event messages to
Monitoring Stations such as:
The events reported to each of the two Monitoring Stations C.S.1 and C.S.2 and corresponding backups.
The communication means (channel) used for the reporting and the backup means (channel) in case of failure.
The customer's (subscriber) account number(s) to be reported to each Monitoring Station.
The IP addresses, SMS numbers and reporting formats of the corresponding alarm receivers at the two Monitoring
Stations C.S.1 and C.S.2 and the number of reporting retry attempts in case of failure to report.
The communication Auto Tests and communication Fail reports.
The reporting of certain system function events such as Confirmed Alarm, Recent Close, Zone Restore and System
Not-Used.
04:COMMUNICATION
3:C.S.REPORTING
MENU item
Enter
3:C.S.REPORTING
, select the menu you wish to configure (see guidance above and in section 4.6.1), then refer
to the table below which provides you with detailed explanations and configuration instructions for each option.
Option
Configuration instructions
01:REPORT EVENTS
Define which events (i.e.
Alarms (alrm)
;
Open/close (o/c)
;
Alerts (alrt)
;
All events (all)
;
Maintenance
and
Troubles
) will be reported to the Monitoring Stations.
The minus (-) symbol means less/except e.g.
all(-alrt)
means
all
events except
alerts
.
The asterisk (
) is a separator between events reported to
Monitoring Station 1
(C.S.1) and
events reported to
Monitoring Station 2
(C.S.2). For detailed and more complete explanation
see the
Event Reporting Chart
at the end of this section.
Options:
all-o/c
backup
(default)
all-o/c
o/c
disable report
all
all
all(-alrt)
alrt
all
backup
all-o/c
all-o/c
alrm
all(-alrm)
Note:
Alarm events (
alrm
) have highest priority and Alert events (
alrt
) have lowest priority.
02:1st RPRT CHAN
If the system is equipped also with Cellular communicators, you must define which of the
communicating channels (i.e. Cellular or Broadband) the system will use as the main channel
(i.e. 1
st
priority) for reporting event messages to Monitoring Stations.
Enter the 1
st
RPRT CHAN; option and define which of the communication channels the
system will use as the main reporting channel.
Options:
broadband first
(default);
disable
; and
cellular first
.
Important:
If the selected main reporting channel fails, the system will use the other
communication channel to report event messages to Monitoring Stations.
If none
is selected, the reporting to Monitoring Stations will be disabled
.
05:DUAL REPORT
Define whether or not to report events using broadband and cellular communication channels.
Options:
disable
(default)
;
broadbnd & cell
.
11:RCVR1 ACCOUNT
Enter the respective 1
st
Account (subscriber) number (11:RCVR 1 ACCOUNT) that will