![Vimar 01527 Скачать руководство пользователя страница 75](http://html.mh-extra.com/html/vimar/01527/01527_installer-manual_1027582075.webp)
75
9.11 Communication objects — Presence detector — Monitoring
9.11.1 Px: Enable movement
Number
Name
Object function
Data type
1 | 19 | 37 | 53
Px: Enable movement
Input
1.001 switch
The detector can be blocked or enabled via the object. Enabling has priority over all other objects.
9.11.2 Px: Monitoring
Number
Name
Object function
Data type
15 | 33 | 51 | 67
Px: Monitoring
Output
1.001 switch
The programmed value is sent to the actuator via the output during movement and after expiry of the switch-off delay (2 seconds).
9.12 Communication objects — Presence detector — Constant light switch
9.12.1 P1: Output 1
Number
Name
Object function
Data type
P1: Output 1
1.001 switch
5.001 percentage (0...100%)
5.010 counter pulses (0...255)
18.001 scene control
20.102 HAVC mode
9.* 2-byte float value
The parameterized value during movement is sent to the actuator via the output when the parameterized brightness threshold including the hysteresis is
exceeded or falls short. When output 2 is active, output 1 is to activated the light row with the largest distance to the window and output 2 with the smallest
distance to the window.
9.12.2 Px: Output 2
Number
Name
Object function
Data type
Px: Output 2
1.001 switch
5.001 percentage (0...100%)
5.010 counter pulses (0...255)
18.001 scene control
20.102 HAVC mode
9.* 2-byte float value
The parameterized value during movement is sent to the actuator via the output when the parameterized brightness threshold including the hysteresis is
exceeded or falls short. When output 2 is active, output 1 is to activated the light row with the largest distance to the window and output 2 with the smallest
distance to the window.
9.12.3 Px: Automatic / manual off
Number
Name
Object function
Data type
Px: Automatic / manual off
1.001 switch
The control can be activated (automatic) or deactivated (manual) via the object. If the object is connected to a control element, the device is switched off with
a 0 and the control is deactivated.
Description of application and parameters
Communication objects - Presence detector - Monitoring