9.8.9 Heating control - P-component (x 0.1°C)
Options:
Setting option between 10 - 100
- The P-component refers to the proportional band of a control. It fluctuates around the setpoint value and can be used to influence control speed with a PI
controller. The smaller the set value, the faster it reacts to the control. However, to avoid the risk of an overshoot, this value should not be set too low. A P-
component from 0.1 to 25.5 K can be set.
Note:
This parameter is only available when "Control value type" parameter is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil". In addition, the
"Heating type" parameter must set on "Free configuration".
9.8.10 Heating control - I-component (min.)
Options:
Setting option between 0 - 255
- The I-component refers to the reset time of a control. The integral component has the effect of moving the room temperature slowly toward, and ultimately
reaching, the setpoint value. Depending on the type of system used, the reset time has to have different values. In general, the more inactive the overall
system, the greater the reset time.
Note:
This parameter is only available when "Control value type" parameter is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil". In addition,
the "Heating type" parameter must set on "Free configuration".
9.8.11 Heating control - Extended settings
Options:
No
Yes
- This parameter enables additional functions and communication objects, e.g. "Basic stage heating".
9.8.12 Basic stage heating
Note:
Only available when the "Extended settings" parameter under "Heating control" is set on "Yes".
9.8.13 Basic stage heating - Status object heating
Options:
No
Yes
- This parameter enables the "Status heating" communication object.
9.8.14 Basic stage heating - Mode of the control value
Options:
Normal
Inverse
The mode of the control value can be used to adapt the control value to de-energised opened (normal) or de-energised closed (inverse) valves.
-
Normal
: Value 0 means "Valve closed".
-
Inverse
: Value 0 means "Valve open".
9.8.15 Basic stage heating - Hysteresis (x 0.1°C)
Options:
Setting option between 3 - 255
- The hysteresis of the two-point controller specifies the fluctuation range of the controller around the setpoint value. The lower switching point is located at
"Setpoint value minus hysteresis" and the upper point is at "Setpoint value plus hysteresis".
Note:
This parameter is only available when the "Control value type" parameter is set either on "2-point 1 Bit, Off/On" or 2-point 1 Byte, 0/100%".
Description of application and parameters
"RTC object" application