9.4 Constant light switch application
9.4.1 General parameters - Output is of type
Options:
1 bit
1 byte 0...100%
1 byte 0...255
Light scene number (1-64)
RTC operating mode switchover (1 byte)
2-byte float
-
1 bit
: Intended for switch actuators.
-
1 byte 0...100%
: For activating dimmers.
-
1 byte 0...255
: For actuators, which are activated with a value of between 0 and 255.
-
Light scene number (1-64)
: For activating light scenes.
-
RTC operating mode switchover (1 byte)
: To directly switch room temperature controllers into a specific operating mode.
› Auto
› Comfort
› Standby
› ECO
› Frost/heat protection
-
2-byte float
: To send a specific temperature for example.
Note:
If the type of output is changed, also the options for setting the parameters change.
› Value for switching on output 1
› Value for switching off output 1 and when they are activated also for:
› Value for switching on output 2
› Value for switching off output 2
In this manual only values for the 1-bit setting are described.
9.4.2 General parameters - Cyclic sending of value for switch-on
Options:
No
Yes
-
No
: The set value is sent only once via the bus.
-
Yes
: The set value is sent cyclic via the bus.
- Parameter "cyclic repeat time" is also displayed.
9.4.3 General parameters - Cyclic repeat time (hh:mm:ss)
Options:
0.00.10 .. 0.00.30 .. 18.12.15
- Here the time which lies between the sending of two telegrams is set.
9.4.4 General parameters - Value for switching on output 1
Options:
On
Off
-
On
: When the presence detector detects movement, value 1 is sent via the bus.
-
Off
: When the presence detector detects movement, value 0 is sent via the bus.
9.4.5 General parameters - Value for switching off output 1
Options:
Off
On
-
Off
: If movement is no longer detected and the switch-off delay has expired, value 0 is sent via the bus.
-
On
: If movement is no longer detected and the switch-off delay has expired, value 1 is sent via the bus.
Description of application and parameters
"Constant light switch" application