9.5.29 Extended parameters - Control speed adjustment through blind inputs
Options:
No
Yes
-
No
: There are no separate settings for adjusting the control speed when a Venetian blind control unit is available.
-
Yes
: There are separate settings: control parameters for the movement of blinds. If a blind now moves up or down, the control speed is adjusted by the
constant light controller during the travel time.
9.5.30 Extended parameters - Total movement time of blind / roller blind (hh:mm:ss)
Options:
0.00.01 .. 0.03.00 .. 1.40.00
- Here the time is specified how long it takes until the shading has been carried out completely (blind/roller blind closed).
9.5.31 Extended parameters - Dimming step size brighter (1 to 15)
Options:
1 .. 15
- Here the step size for increasing the dimming value during blind movement is specified.
Note:
If the dimming step size is set too high, the dimming steps will be clearly visible in the lighting.
9.5.32 Extended parameters — Dimming step size darker (1 - 15)
Options:
1 .. 4 .. 15
- Here the step size for reducing the dimming value during blind movement is specified.
Note:
If the dimming step size is set too high, the dimming steps will be clearly visible in the lighting.
9.5.33 Extended parameters - Control speed (mm:ss)
Options:
0.45 .. 2.30 .. 20.00
- Here the time is specified which the control requires to get from 0 to the upper limit output value.
Example: If the control speed is on 10:00 and the lighting is switched on with 50% and the upper limit is 100%, the control requires 5 minutes to get from 50%
to 100%. Vice versa, the control requires 10 minutes to regulate from 100% to 0%.
9.5.34 Extended parameters - Actual brightness filter
Options:
rFast, approx. 15 seconds
Normal, approx. 40 seconds
Slow, approx. 75 seconds
- The application reacts to brightness fluctuations (e.g. clouds). The more inactive the filter is set, the slower the lighting will respond to such fluctuations.
9.5.35 Extended parameters - Exiting manual off dimming mode after (hh:mm)
Options:
0.05 .. 1.00 .. 12.00
- When the presence detector receives a value via the relative dimming (dimmer) object or a value > 0 via the value (dimmer) object, the presence detector
will no longer function automatically. The presence detector is switched back to automatic mode only after the movement detected last and the expiry of
the set time.
9.5.36 Extended parameters - Exiting manual off mode after (hh:mm)
Options:
0.05 .. 1.00 .. 12.00
- When the presence detector receives a switch-off value via the switching (dimmer) object or a value = 0 via the value (dimmer) object, the presence detec-
tor is switched off and will no longer switch on automatically. The presence detector will function again automatically only after the receipt of value 1 on the
switching (dimmer) object or after the movement detected last and the expiry of the set time.
Description of application and parameters
"Constant light controller" application