9.8.100 Temperature reading — Operating mode for fault
Options:
Cooling
Heating
In the event of a failure of the actual temperature measurement, the device will no longer be able to independently specify the heating/cooling operating
type. As a result, the operating type best suited to protecting the building will be selected.
Note:
This parameter is only available when the "Control function" parameter is set on "Heating and cooling" or "heating and cooling with additional stages".
9.8.101 Temperature reading - Control value for fault (0 - 255)
Options:
Setting option between 0 - 255
In the event of a failure of the actual temperature measurement, the device will no longer be able to independently determine the control value. Therefore, a
control value which is suitable for protecting the building will be selected.
9.8.102 Alarm functions
Note:
This parameter is only available if the "Device function" parameter is set on either "Single device" or "Master device".
9.8.103 Alarm functions - Condensate water alarm
Options:
No
Yes
If a fan coil is used, condensation may form during operation as a result of excessive cooling and/or humidity. The associated condensate is typically col-
lected in a container. To protect the container against overflowing, and thus prevent potential damage to devices and/or the building, the container alerts
the "Condensation alarm" object (receiving only) that the maximum fill level has been exceeded. This causes the controller to switch to a protective mode.
This status is indicated by the corresponding icon on devices that have a display. Local operation is blocked.
Operation is only possible again after the alarm has been deactivated.
Note:
This parameter is only available when the "Control function" parameter is set either on "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
9.8.104 Alarm function — Dew point alarm
Options:
No
Yes
When refrigerating machines are used, dew may appear on the refrigerant supply lines during operation as a result of excessive cooling and/or humidity.
The dew indicator reports the dew formation via the "Dew point alarm" object (receiving only). This causes the controller to switch to a protective mode. This
status is indicated by the corresponding icon on devices that have a display. Local operation is blocked. Operation is only possible again after the alarm
has been deactivated.
Note:
This parameter is only available when the "Control function" parameter is set either on "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
9.8.105 Alarm functions - Frost alarm temperature for HVAC and RHCC status (°C)
Options:
Setting option between 0 - 15
The RHCC status and HVAC objects have a frost alarm bit. It the input temperature of the controller drops below the temperature set in this parameter, then
the frost alarm bit is set in the status objects. It is reset when the temperature is exceeded.
9.8.106 Alarm functions - Heat alarm temperature for RHCC status (°C)
Options:
Setting option between 25 - 70
The RHCC status object has a heat alarm bit. If the input temperature of the controller exceeds the temperature set in this parameter, then the heat alarm
bit is set in the status object. It is reset when the temperature falls below the set temperature.