![Vimar 01527 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/vimar/01527/01527_installer-manual_1027582006.webp)
6
3. Product description
3.1 Device overview
24V
1
2
4
3
3
4
A
C
B
2
1
Fig. 1: Product overview
A Programming button
B Sensor for brightness detection
C Programming LED
1, 2, 3, 4 Individual sectors with switch-off function (via parameter setting).
For numbering see the rear of the device
This device is a presence or movement detector which is designed only for interior areas of buildings. The devices serve for switching and regulating lighting systems
and/or HKL (HVAC) systems in dependence of brightness and/or movement. It makes possible the specific deactivation and activation of light rows in dependence
of the brightness of the room. Also dimming/regulating the brightness to a defined value in a designated detection range with the corresponding device is possible.
The integrated bus coupler makes possible the connection of a KNX bus line.
The device can be mounted either in the ceiling via hollow-wall mounting or on the ceiling via the optionally available surface-mounted housing (article 01529.1.S
and 01527.S). The mounting instructions are enclosed with the surface-mounted housing. The overall function of the device also depends on the mounting height.
Note
The device does not fit in the BS and VDE flush-mounted box.
Recommendation:
• HaloX-O flush-mounted box from Kaiser (article no. 1290-40) with corresponding cover (article no. 1290-47 or article no. 1290-85 for exposed concrete)
• IBTronic H120-68 from Spelsberg (article no. 97600501)
The detection range can additionally be adapted via individual sectors with switch-off function (via parameter setting).
Note
The unit contains highly sensitive sensors and lens systems.
- Do not cover or mask lens segments since this will interfere with the function of the device.
- Do not clean the device and the lens system with abrasive or aggressive cleaning agents.
3.2 Overview of types
Article no.
Detection range
Usage
Mounting height
01527
Circular
(details under 'Technical Data')
For detection range of up to 8 m individual rooms (e.g. office, living room,
etc.).
Wherever increased functionality is required.
2,5 m, 3 m and 4 m
01529.1
Circular
(details under 'Technical Data')
For detection range of up to 12 m large rooms (e.g. large-scale office, class-
rooms, etc.). Wherever functionality is not greatly in demand.
2,5 m, 3 m and 4 m
Product description