9.16.26 Fan speed level 4
Number
Name
Object function
Data type
24
Fan speed level 4
Output
Switching
This 1-bit communication object is used to output the active status (1) of the fan speed level, while the other fan speed levels are deactivated (0), depending
on the parameter setting. If the fan speed level is inactive, the object has a value of (0).
9.16.27 Fan speed level 5
Number
Name
Object function
Data type
25
Fan speed level 5
Output
Switching
This 1-bit communication object is used to output the active status (1) of the fan speed level, while the other fan speed levels are deactivated (0), depending
on the parameter setting. If the fan speed level is inactive, the object has a value of (0).
9.16.28 Basic set value
Number
Name
Object function
Data type
26
Basic set value
Input
2-byte floating point value
This 2-byte communication object can be used to change/adjust the parameterized basic setpoint value via the KNX bus. Parameters can be used to
define whether the value received by this object is interpreted as "Setpoint heating comfort", "Setpoint cooling comfort" or an average between heating
and cooling comfort.
9.16.29 Resetting manual set values
Number
Name
Object function
Data type
27
Resetting manual set values
Input
Switching
This 1-bit communication object is used to reset the manual setpoint adjustment that was set on the device.
9.16.30 Dew point alarm
Number
Name
Object function
Data type
28
Dew point alarm
Input
Switching
This 1-bit communication object is used to place the controller in the dew point alarm mode. This causes the current setpoint value to be set to the heat
protection setpoint value in order to keep the structure from being damaged by dew.
Note:
This protective mechanism is only active in the cooling mode. It remains in place until it is cancelled by the value (0). When an alarm is active, manual opera-
tion of the controller is blocked. This information is indicated by a corresponding icon on the control unit.
9.16.31 Condensate water alarm
Number
Name
Object function
Data type
29
1. Condensate water alarm
Input
Switching
2. Condensate water alarm (master/slave)
Input
Switching
This 1-bit communication object is used to place the controller in the condensation alarm mode. This causes the current setpoint value to be set to the heat
protection setpoint value in order to keep the structure from being damaged by an overflowing condensation container.
Note:
Item 1:
This protective mechanism is only active in the cooling mode. It remains in place until it is cancelled by the value (0). When an alarm is active, manual opera-
tion of the controller is blocked. This information is indicated by a corresponding icon on the device.
Item 2:
• This protective mechanism is only active in the cooling mode. It remains in place until it is cancelled by the value (0). When an alarm is active, manual
operation of the controller is blocked. This information is indicated by a corresponding icon on the device.
• When the master/slave mode is active, the condensate water alarm (master/slave) objects must be connected to the alarm transmitter.
Description of application and parameters
Communication objects - Object RTC