9.6.13 Extended parameters - Use of object for force-position
Options:
No
Yes
-
No
: There is no separate force-position object.
-
Yes
: There is a separate 1-bit force-position object (input). When an On telegram is received via the object, the presence detector is blocked and the value
under force-position is sent via the HVAC object. If an Off telegram is received via the object, the presence detector is enabled again. If a movement is then
detected, the value for switch-on is sent. If no movement occurs, the value for switch-off is sent.
Value for force-position
Options:
Auto
Comfort
Standby
ECO
Frost/heat protection
- Here it is specified what is to be sent when the force-position object receives an On telegram.
9.6.14 Extended parameters — Overwriting settings during a download
Options:
Yes
No
-
Yes
: When the application is reloaded into the detector, the values changed via the bus are overwritten with the parameterized values of the ETS application.
-
No
: When the application is reloaded into the detector, the values changed via the bus are not overwritten with the parameterized values of the ETS ap-
plication.
Values:
• Switch-on delay
• Switch-off delay
9.6.15 Sensor selection - Use of sensors 1 - 4
Options:
Yes
No
-
Yes
: This sensor is active and detects movement.
-
No
: This sensor is switched off and movement is no longer detected in this area.
9.6.16 Enable - Use of enable object
Options:
No
Yes
-
No
: There is no object with which the HVAC control can be blocked or enabled.
-
Yes
: A 1-bit enable heating, ventilation and air-conditioning communication object (input) is being enabled. This object allows the HVAC control to be enabled
or blocked. No telegrams are sent by the detector during blockage.
9.6.17 Enable - Enable with
Options:
ON telegram
OFF telegram
-
ON telegram
: With the receipt of value 1 on the enable movement (input) object the detector is enabled and blocked with value 0.
-
OFF telegram
: With the receipt of value 0 on the enable movement (input) object the detector is enabled and blocked with value 1.
Description of application and parameters
Application "HVAC" (Heating, ventilation, air-conditioning)