43
9.5.37 Extended parameters - Pause time (ss.fff)
Options:
00.100 .. 01.250 .. 59.999
- The set pause time is started after the detector has been switched off due to expiry of the switch-off delay or when a switch-off telegram is received on
objects external push-button or actuator status.
If movement is detected during this time, the detector is not switched on immediately. The pause time is first extended by 7 seconds. If there is still movement
after these 7 seconds, the detector switches back on.
If no movement is detected during the pause time, the detector is ready for activation again after the pause time.
This behaviour can, for example, be important when the lamp cools down drastically and is located within the detection range of the detector. Without a
blockage there would be an unintentional switch-on. The purpose of pause time is to prevent an immediate re-activation.
Example: The person switches the light off manually when leaving the room. Without the pause time the detected movement would cause a renewed switch-
on during exiting.
Note:
› The external push-button object is activated under the "External push-button" parameter.
› The actuator status object is activated under the status display parameter.
9.5.38 Extended parameters - Use of status of control object
Options:
No
Yes
-
No
: There is no separate status of control object.
-
Yes
: A 1-bit status of control communication object (output) is being enabled. This object sends a 1 telegram when the constant light controller functions
automatically. The object sends a 0 telegram when manual action takes place, e.g. if a manual switch-off has taken place.
9.5.39 Extended parameters — Overwriting settings during a download
Options:
Yes
No
-
Yes
: When the application is reloaded into the detector, the values changed via the bus are overwritten with the parameterized values of the ETS application.
-
No
: When the application is reloaded into the detector, the values changed via the bus are not overwritten with the parameterized values of the ETS ap-
plication.
Values:
• Set value
• Switch-off delays
• Brightness correcting values
9.5.40 Sensor selection - Use of sensors 1 - 4
Options:
Yes
No
-
Yes
: This sensor is active and detects movement.
-
No
: This sensor is switched off and movement is no longer detected in this area.
9.5.41 Enable - Use of presence detector enable object
Options:
No
Yes
-
No
: There is no object with which the constant light controller can be blocked or enabled.
-
Yes
: A 1-bit enable presence communication object (input) is being enabled. This object allows the constant light controller to be enabled or blocked. No
telegrams are sent by the detector during blockage.
Description of application and parameters
"Constant light controller" application