9.8.87 Setpoint adjustment - Resetting of the manual adjustment for receipt of a basic set value
Options:
No
Yes
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint value to be provided when a new value is received via the
"Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21 °C + manual adjustment of 1.5°C = 22.5°C. The object receives a new basic setpoint of 18°C plus the previous
manual adjustment of 1.5°C for a total of 19.5°C.
9.8.88 Setpoint adjustment - Resetting the manual adjustment for change of operating mode
Options:
No
Yes
If the device switches to a new operating mode, the manual adjustment is deleted and the parameterized setpoint temperature for the operating mode plus
any change by the base setpoint value object will be applied if this parameter is activated. Example: Comfort temperature of 21°C plus manual adjustment of
1.5°C = 22.5°C. Change to Eco with programmed temperature 17°C. The device regulates the temperature to 17°C, since the manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the temperature in the new operating mode. Example: Comfort temperature of
21°C plus manual adjustment of 1.5°C = 22.5°C. If the system switches to Eco with a parameterized temperature of 17°C, the device regulates the temperature
to 18.5°C, since the manual adjustment is added.
9.8.89 Setpoint adjustment - Resetting the manual adjustment via object
Options:
No
Yes
If this parameter is activated, a separate object can be used to delete the manual adjustment at any time. Example of application: Resetting the manual adjust-
ment on all devices located in a building using a system clock.
9.8.90 Setpoint adjustment - Permanent storage of on-site operation
Options:
No
Yes
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed level, as well as the value of the "Basic load" object, will be
stored in the device and re-activated after a reset. If the device is re-programmed, the stored setpoint values will also be deleted.
9.8.91 Temperature reading - Inputs of temperature reading
Options:
Internal measurement
External measurement
Weighted measurement
The room temperature can be measured at the device or fed to the device by an object via the bus. In addition, weighted measuring is also available, in which
the weighted average of up to three temperature values (1 x internal, 2 x external) is calculated and used as an input value for control.
9.8.92 Temperature reading - Inputs of weighted temperature reading
Options:
Internal and external measurement
2 x external measurement
Internal and 2x external measurement
Specifies the temperature reading inputs for the weighted measurement, in which the calculated weighted average of the inputs is used as an input value for
control
Note:
This parameter is only available when the "Inputs of temperature reading" parameter is set on "Weighted measurement".
Description of application and parameters
"RTC object" application