9.8.93 Temperature reading - Weighting of internal measurement (0 to 100%)
Options:
Setting option between 0 - 15
Specifies the weighting of the internal measurement at a level between 0% and 100%.
Note:
This parameter is only available when the "Inputs of weighted temperature reading" parameter is set on "Internal and external measurement" or "Internal and
2x external measurement".
9.8.94 Temperature reading - Weighting of external measurement (0 to 100%)
Options:
Setting option between 0 - 15
Specifies the weighting of the external measurement at a level between 0% and 100%.
Note:
This parameter is only available when the "Inputs of weighted temperature reading" parameter is set on "Internal and external measurement","2x external
measurement" or "Internal and 2x external measurement".
9.8.95 Temperature reading - Weighting of external measurement 2 (0 to 100%)
Options:
Setting option between 0 - 15
Specifies the weighting of the external measurement 2 at a level between 0% and 100%. When added together with the (0%...100%) weighting of the external
measurement, the result must be 100%.
Note:
This parameter is only available when the "Inputs of weighted temperature reading" parameter is set on "2x external measurement" or "Internal and 2x external
measurement".
9.8.96 Temperature reading - Cyclic sending of the actual temperature (min)
Options:
Setting option between 5 - 240
The current actual temperature used by the device can be cyclically transmitted to the bus.
9.8.97 Temperature reading - Difference of value for sending the actual temperature (x 0.1°C)
Options:
Setting option between 1 - 100
If the change in temperature exceeds the parameterized difference between the measured actual temperature and the previous actual temperature that was
sent, the changed value will be transmitted.
9.8.98 Temperature reading - Adjustment value for internal temperature measurement (x 0.1°C)
Options:
Setting option between 1 - 100
Every installation location has different physical conditions (interior or exterior wall, lightweight or solid wall, etc.). In order to use the actual temperature at
the installation location as a measured value for the device, a temperature measurement must be performed by an external equalised and / or calibrated
thermometer at the installation location. The difference between the actual temperature displayed on the device and the actual temperature determined by
the external measurement device must be entered in the parameter field as an "Adjustment value".
Note:
› The calibration measurement should not be carried out immediately after the device has been installed. The device should first adjust to the ambient tem-
perature before calibration is carried out. The calibration measurement should be repeated shortly before or after the room is occupied.
› This parameter is only available when the "Inputs of temperature reading" parameter is set on "Internal measurement" or "Weighted measurement".
9.8.99 Temperature reading - Monitoring time for temperature reading (0 = no monitoring) (min)
Options:
Setting option between 0 - 120
If no temperature is read within the parameterized time period, the device switches to error mode. It transmits a telegram to the bus via the "Actual temperature
error" object and applies the operating mode and control value for error settings.
Description of application and parameters
"RTC object" application