70
9.8.114 Fan coil settings for heating - Speed level 1 to 5 up to control value (0 to 255) heating
Options:
Setting option between 0 - 255
In this parameter, the control values of the controller are assigned to fan speed levels. This assignment is used if the fan speed levels are transmitted together
with the control values.
Note:
› These level settings should be adjusted to match the settings in the fan coil actuator.
› Setting the "Control value type" to "Fan coil" in the control parameters is only useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the control of only one fan coil actuator each for heating and cooling is supported.
› The "Fan speed level 4 - 5 up to control value (0 - 255) heating“ parameters are available only when the "Number of fan speed levels" is set on "5 steps".
9.8.115 Fan coil settings for heating - Fan speed level limit heating in eco mode
Options:
No
Yes
This parameter limits the fan speed level when the system is switched to eco mode.
9.8.116 Fan coil settings for heating - Maximum speed level heating for eco mode
Options:
Setting option between 0 - 5
Specifies the maximum possible fan speed level when the system is switched to eco mode.
9.8.117 Fan coil settings cooling
Note:
This parameter is only available if the "Device function" parameter is set on either "Single device" or "Master device" and the "Control value type" parameter
is set on "Fan coil". In addition, the "Control function" parameter must be set on either "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
9.8.118 Fan coil settings for cooling - Speed level 1 to 5 up to control value (0 to 255) cooling
Options:
Setting option between 0 - 255
In this parameter, the control values of the controller are assigned to fan speed levels. This assignment is used if the fan speed levels are transmitted together
with the control values.
Note:
• These level settings should be adjusted to match the settings in the fan coil actuator.
• Setting the "Control value type" to "Fan coil" in the control parameters is only useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the control of only one fan coil actuator each for heating and cooling is supported
• The "Fan speed level 4 - 5 up to control value (0 - 255) cooling“ parameters are available only when the "Number of fan speed levels" is set on "5 steps".
9.8.119 Fan coil settings for cooling - Fan speed level limit cooling in eco mode
Options:
No
Yes
This parameter limits the fan speed level when the system is switched to eco mode.
9.8.120 Fan coil settings for cooling - Maximum speed level cooling for eco mode
Options:
Setting option between 0 - 5
Specifies the maximum possible fan speed level when the system is switched to eco mode.
9.8.121 Summer compensation
Note:
This parameter is only available if the "Device function" parameter is set on either "Single device" or "Master device".
Description of application and parameters
"RTC object" application