38
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.9
ID Control Functions
6.9.1
Value control
Table 1.
Power reference input signal selection, G2.2.8
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.9.1.1
Control Input Signal
ID
0
10000
ID
0
1580
P2.9.1.2
Control Input Off
Limit
-32000
32000
0
1581
P2.9.1.3
Control Input On
Limit
-32000
32000
0
1582
P2.9.1.4
Control Output Off
Value
-32000
32000
0
1583
P2.9.1.5
Control Output On
Value
-32000
32000
0
1584
P2.9.1.6
Control Output Signal
ID
0
10000
ID
0
1585
P2.9.1.7
Control Mode
0
5
0
1586
0 = SR ABS
1 = Scale ABS
2 = Scale INV ABS
3 = SR
4 = Scale
5 = Scale INV
P2.9.1.8
Control Output
Filtering rime
0.000
32.000
s
0.000
1721
6.9.2
DIN ID Control 1
Table 2.
DIN ID control parameters, G2.2.8
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.9.2.1
ID Control DIN
0.1
E.10
0.1
1570
Slot Board input No.
If
0.1
ID61
can
be
controlled from FB
P2.9.2.2
Controlled ID
0
10000
ID
0
1571
Select
ID
that
is
controlled by digital input
P2.9.2.3
False value
-32000
32000
0
1572
Value when DI is low
P2.9.2.4
True value
-32000
32000
0
1573
Value when DI is high
Содержание NX ACTIVE FRONT END II
Страница 1: ...vacon nx ac drives active front end ii afe ii arfiff05 application manual ...
Страница 2: ......
Страница 93: ......
Страница 94: ......