Arfiff05 Standard AFE-II
vacon •
43
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
P2.3.1.7
Run Enable
ID407
This parameter defines which digital input is used for external Run Enable signal. If Run
Enable is used the drive does not go to Ready state until the Run Enable goes high.
P2.3.1.8
Quick Stop (Power Down)
ID1213
Drive is stopped and MCB is opened immediately and DC needs to go zero to make
restart. Power Down command with a warning indication (Recorded to fault history).
P2.3.1.9
Ext. Fault 1
ID405
P2.3.1.10 Ext. Fault 2
ID406
This parameter defines if the drive monitors the status of the External fault input. The
response to the fault can be selected with the parameter
.
P2.3.1.11 Fault Reset
ID414
This parameter defines which digital input is used to reset faults.
P2.3.1.12 LC Cooling
ID750
OK input from the cooling unit. Warning indication if unit is not in run state or there is not
active run request. Response is fault within 3 second if unit is in run state or there is an
active run request.
P2.3.1.13 MCB Trip State
ID1706
Input signal for Main Circuit Breaker trip state. Gives F64 with and subcode.
Содержание NX ACTIVE FRONT END II