Arfiff05 Standard AFE-II
vacon •
19
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.1.4
Master Follower
Code
Parameter
Unit
Form.
ID
Description
V1.4.1
SB SystemStatus
1601
V1.42
Master CW
93
5.1.5
Monitoring values 2
Code
Signal
Unit
ID
Description
V1.5.1
Measured temperature 1
Cº
50
4 s filtering.
V1.5.2
Measured temperature 2
Cº
51
4 s filtering.
V1.5.3
Measured temperature 3
Cº
52
4 s filtering.
V1.5.4
Measured temperature 4
Cº
69
4 s filtering.
V1.5.5
Measured temperature 5
Cº
70
4 s filtering.
V1.5.6
Measured temperature 6
Cº
71
4 s filtering.
V.1.5.7
PT-100 Temperature
Cº
42
Highest temperature of OPTB8/OPTBH board. 4 s
filtering.
5.2
Monitoring Values description
5.2.1
Monitoring 1 values
V1.1.1
DC-Link Voltage
Vdc
ID44
Measured DC voltage, filtered.
V1.1.2
DC-Link Ref.
Vdc
ID25
DC-Link voltage reference in Vdc.
V1.1.3
DC Voltage Ref.
%
ID1200
Used DC Voltage reference in %
V1.1.4
DC Voltage Act.
%
ID7
Actual DC Voltage in %
V1.1.5
Total Current
A
ID3
Total current of the regenerative unit in Amperes, filtered
V1.1.6
Active Current
%
ID1125
Active current in % of System Rated Current.
Negative value means that current is flowing to AC side from DC side i.e. regenerating.
V1.1.7
Reactive Current
%
ID1157
Reactive current of the regenerative drive in % of System Rated Current.
Positive is Inductive current.
Negative is capacitive current.
V1.1.8
Supply Frequency
Hz
ID1
Supply frequency in ##.## Hz .The sign indicates the phase order. Updated when drive in
run state. Updated also in stop state when OPT-D7 is used or Regen Options B9 is
activated.