6.
PARAMETER LIST
6.1
Basic parameters
Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.1.1
Grid Nominal Voltage
500V:
380V
690V:
525V
500V:
500V
690V:
690V
V
400
110
Set here the nominal voltage of
the grid.
P2.1.2
Grid Nominal
Frequency
48
63
Hz
50
1532
Set
here
the
nominal
frequency of the grid.
P2.1.3
System Rated Current
0,0
Ih
A
Ih
113
Capacity of supply, used if
oversized AFE.
P2.1.4
System Rated Power
0
32000
kW
0
116
P2.1.5
Parallel AFE
0
3
0
1501
0 = Single AFE
1 = Parallel AFE
1 = Master
1 = Follower
Table 5-2. Basic parameters
6.2
Reference Handling
Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.2.1
DC Voltage Ref.
105
Varies
%
110,00
1462
DC Voltage reference as % of
Nominal DC Voltage
Nominal DC voltage = 1,35 *
Supply voltage
P 2.2.2
DC Voltage Drooping
0,00
100,00
0,00
620
AFE drooping DC-voltage. Set
to 3,00 % when parallel AFE
operation is selected
P2.2.3
Reactive Current
Reference
-100,0
100,0
%
0,0
1459
Regenerative reactive current
reference 100,0 = nominal
current.
Positive =Inductive
Negative = Capacitive
P2.2.4
DC Reference Offset
-5,00
5,00
%
0,00
1777
Table 1- 1, Reference Handling