34
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.6
Drive Control parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.1
AFE Options 1
0
65535
544
1463
P2.6.2
AFE Options 2
0
65535
0
1464
P2.6.3
Control Options
0
65536
0
1707
Control word for activating
special features.
P2.6.4
Start Delay
0,00
320,00
s
0,50
1500
Starting delay when run
command is given. When
programming different
delay to paralleled units,
the units will start in
sequence.
P2.6.5
Modulator Type
0
4
Single:
2
Parallel
1
1516
0 = Hardware
1 = Software 1
2 = Software 2
3 = Software 3
4 = Software 4
P2.6.6
Operation Time
0
2^32
1855
Table 5-6. Drive control parameters G2.4
6.6.1
Control
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.7.1
Capacitor Size
0
100
%
6,3
1460
P2.6.7.2
Inductor Size
0
100
%
15,5
1461
P2.6.7.3
Dynamic Support Kp
0
32000
0
1797
P2.6.7.4
Synch Kp
0
32000
2000
1457
P2.6.7.5
Synch Ti
0
1000
50
1458
P2.6.7.6
Active Current Kp
0
4000
400
1455
P2.6.7.7
Active Current Ti
0,0
100,0
1,5
1456
P2.6.7.8
Synch. Kp Start
0
10000
4000
1300
P2.6.7.9
Voltage Ctrl Kp
0
32000
200
1451
P2.6.7.10
Voltage Ctrl Ti
0
1000
ms
50
1452
P2.6.7.11 Switching Frequency
3,4
Varies
Hz
3,6
601
Table 5-6. Drive control parameters G2.4