Arfiff05 Standard AFE-II
vacon •
71
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8.2.2
Vacon AFE 1 profile (2)
FB Control Word ID1160
Signal
Comment
B00
DC Charge
0= Open MCB.
1= Close DC charge contactor, MCB closed automatically.
B01
B02
B03
Run
0= AFE is stopped
1= AFE is started
B04
B05
B06
B07
Reset
0>1 Reset fault.
B08
DC Voltage Ref B00
B00 | B01
0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %
0 | 1 = 110 %
1 | 0 = 115 %
1 | 1 = 120 %
B09
DC Voltage Ref B01
B10
Fieldbus Control
0= No control from fieldbus
1=Control from fieldbus
B11
Watchdog
0,5 sec square wave clock. This is used to check data
communication between fieldbus master and the drive.
B12
FB DIN2
Can be used to control RO or directly parameter by ID number. G2.4.1
B13
FB DIN3
Can be used to control RO or directly parameter by ID number. G2.4.1
B14
FB DIN4
Can be used to control RO or directly parameter by ID number. G2.4.1
B15
Reserved for future use.
B00: FALSE = Open MCB, TRUE = PreCharge DC
Open MCB: Opens MCB if closed, stops precharging if not closed.
PreCharge DC: Drive will start precharge if function activated by digital output and control place is
fieldbus. When control place is not fieldbus precharging is started from normal start command.
B03: FALSE = Stop Request, TRUE = Start Request
Stop Request: Drive will stop .
Start Request: Start Command to the drive. Rising edge needed for start.
B07: FALSE = No significance, TRUE = Fault Acknowledge
Fault Acknowledge: The group signal is acknowledged with a positive edge.
B08: FALSE = No Function, TRUE = DC Ref 1
B09: FALSE = No Function, TRUE = DC Ref 2
DC Ref
FB Reference
110,00 %
115,00 %
120,00 %
B08
FALSE
TRUE
FALSE
TRUE
B09
FALSE
FALSE
TRUE
TRUE