STATUS AND CONTROL WORDS IN DETAIL
P2.10.19 State machine
0 / Basic
This mode makes fieldbus control behave as in explained in used
fieldbus board manual.
1 / Standard
Simple control word that is used in modes where control word
from fieldbus is used as such, for some fieldbus board this
requires bypass operation.
2 / Vacon AFE 1
This mode uses ProfiDrive type state machine in application level.
This mode is possible to use on fieldbus boards that does not have
state machine itself or has possibility to bypass state machine
functionality in option board.
3 / Vacon AFE 2
This mode uses ProfiDrive type state machine in application level.
This mode is possible to use on fieldbus boards that does not have
state machine itself or has possibility to bypass state machine
functionality in option board.
8.1
Basic In ByPass (0)
FB Control Word ID1160
Signal
Description
B00
Run
0= AFE is stopped
1= AFE is started
B01
B02
Fault Reset
0>1 Reset fault.
B03
FB DIN1
Can be used to control RO or directly parameter by ID number. G2.4.1
B04
FB DIN2
Can be used to control RO or directly parameter by ID number. G2.4.1
B05
FB DIN3
Can be used to control RO or directly parameter by ID number. G2.4.1
B06
FB DIN4
Can be used to control RO or directly parameter by ID number. G2.4.1
B07
FB DIN5
Can be used to control RO or directly parameter by ID number. G2.4.1
B08
B09
B10
B11
B12
B13
B14
B15