20
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.1.9
Supply Voltage
V
ID6
Input AC voltage, RMS line to line Volts. Updated when drive in run state.
Updates also when OPT-D7 is used.
V1.1.10
Unit Temperature
°C
ID8
Temperature of the unit in degrees Celsius
V1.1.11
Status Word
ID43
Application Status Word combines different drive statuses to one data word.
Application Status Word ID43
FALSE
TRUE
b0
b1
Not in Ready state
Ready
b2
Not Running
Running
b3
No Fault
Fault
b4
b5
Quick Stop Active
Quick Stop Not Active
b6
Run Disabled
Run Enable
b7
No Warning
Warning
b8
Charging Switch closed (internal)
b9
MCB Control (DO Final)
b10
MCB Feedback
b11
DO Charging Active
b12
No Run Request
Run Request
b13
b14
b15
V1.1.12
DIN 645. 321
ID15
DIN1/DIN2/DIN3 status
B0
DIN1
B1
DIN2
B2
DIN3
B3
DIN4
B4
DIN5
B5
DIN6
V1.1.13
Analogue Input 1
%
ID13
V1.1.14
Analogue Input 2
%
ID14
Unfiltered analogue input level.
0 % = 0 mA / 0 V, -100 % = -10 V, 100 % = 20 mA / 10 V.
Monitoring scaling is determined by the option board parameter.
V1.1.15
Analogue Out 1
%
ID26
Analogue Output value 0 % = 0 mA / 0 V, 100 % = 20 mA / 10 V