36
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.7.3
Fieldbus
Code
Parameter
Min
Max
Unit
Default
ID
Description
2.7.3.1
FB Fault Response
0
2
2
733
0=No response
1=Warning
2=Fault
2.7.3.2
FB WD Delay
0,00
30,00
0,00
1354
0,00 = Disabled WD
Table 5-9. Fieldbus Protections parameters G2.7.2
6.7.4
OPT-D7 protections
Code
Parameter
Min
Max
Unit
Default
ID
Description
2.7.4.1
THD Response
0
2
0
1672
2.7.4.2
THD Warn. Limit
0,00
50,00
%
6,00
1673
2.7.4.3
THD Fault Limit
0,00
50,00
%
10,00
1674
2.7.4.4
HF rms Response
0
2
0
1675
2.7.4.5
HF rms Warn Limit
0,0
400,0
V
20,0
1676
2.7.4.6
HF rms Fault Limit
0
400,0
V
60,0
1677
Table 5-9. OPT-D7 Protection parameters G2.7.3
6.7.5
Options
Code
Parameter
Min
Max
Unit
Default
ID
Description
2.7.5
Fault Simulation
0
65535
0
1569
2.7.6
Reset Datalogger
0
1
0
1857
Resets datalogger to
defaults.
Table 5-9. Options parameters G2.7.2