Arfiff05 Standard AFE-II
vacon •
87
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
F31
IGBT temperature
IGBT Inverter Bridge over temperature protection has detected too high a short term overload
current.
Possible cause:
1.
Too high load
2.
Identification run has not been made which causes the motor to start under magnetized.
Correcting measures:
1.
Check load.
2.
Check motor size.
3.
Make identification Run.
F32
Fan cooling
Possible cause:
1.
Cooling fan of the frequency converter does not start when ON command is given.
Correcting measures:
1.
Contact your local distributor.
F37
Device change
Option board or power unit changed.
Possible cause:
1.
New device of same type and rating.
Correcting measures:
1.
Reset. Device is ready for use.
F38
Device added
Option board added.
Correcting measures:
1.
Reset. Device is ready for use. Old board settings will be used.
F39
Device removed
Option board removed.
Correcting measures:
1.
Reset. Device no longer available.
F40
Device unknown
Unknown option board or drive.
S1 = Unknown device
S2 = Power1 not same type as Power2
Correcting measures:
1.
Contact the distributor near to you.