6.5
Limit Settings
6.5.1
Current Limit
Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.5.1.1
Current Limit
0
Varies
A
Varies
107
Total current limit
P2.5.1.2
Output Active
Current Limit
0
300,0
%
150,0
1290
Generating Active Current
limit in AFE mode to grid.
P2.5.1.3
Input Active Current
Limit
0
300,0
%
150,0
1289
Motoring active current limit
in AFE mode to DC-link.
6.5.2
Power Limit
Code
Parameter
Min
Max
Unit
Default
ID
Note
P 2.5.2.1
Output Power Lim
0
300,0
%
150,0
1288
Generating power limit
P 2.5.2.2
Input Power Lim
0
300,0
%
150,0
1287
Motoring power limit
6.5.3
Frequency Limit
Code
Parameter
Min
Max
Unit
Default
ID
Note
P 2.5.3.1
Low Frequency Trip
Limit
42
120
%
80
1717
P 2.5.3.2
High Frequency Trip
Limit
42
120
%
120
1716
6.5.4
AC Voltage Limit
Code
Parameter
Min
Max
Unit
Default
ID
Note
P 2.5.4.1
Low AC Voltage Trip
Limit
50
150
%
80
1711
P 2.5.4.2
High AC Voltage Trip
Limit
50
150
%
120
1710
6.5.5
DC Voltage Limit
Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.5.5.1
DC Super Vision
Limit
0
1300
Vdc
600
1454
P2.5.5.2
High MCB Close
Limit
0
1300
Vdc
0
1251