70
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8.2
FB Control Word
8.2.1
Standard (1)
FB Control Word ID1160
Signal
Comment
B00
DC Charge
0= Open MCB.
1= Close DC charge. MCB closed automatically.
B01
B02
B03
Run
0= AFE is stopped
1= AFE is started
B04
B05
B06
B07
Reset
0>1 Reset fault.
B08
B09
B10
B11
FB DIN1
Can be used to control RO or directly parameter by ID number. G2.4.1
B12
FB DIN2
Can be used to control RO or directly parameter by ID number. G2.4.1
B13
FB DIN3
Can be used to control RO or directly parameter by ID number. G2.4.1
B14
FB DIN4
Can be used to control RO or directly parameter by ID number. G2.4.1
B15
B00: FALSE = Open MCB, TRUE = PreCharge DC
Open MCB: Opens MCB if closed, stops precharging if not closed.
PreCharge DC: Drive will start precharge if function activated by digital output and control place is
fieldbus. When control place is not fieldbus precharging is started from normal start command.
B03: FALSE = Stop Request, TRUE = Start Request
Stop Request: Drive will stop .
Start Request: Start Command to the drive. Rising edge needed for start.
B07: FALSE = No significance, TRUE = Fault Acknowledge
Fault Acknowledge: The group signal is acknowledged with a positive edge.