F41
IGBT temperature
IGBT inverter bridge over temperature protection has detected too high a short term overload
current.
Correcting measures:
1.
Check load.
F44
Device changed (Default param.)
Possible cause:
1.
Option board or power unit changed.
2.
New device of different type or different rating from the previous one.
Correcting measures:
1.
Reset
2.
Set the option board parameters again if option board was changed. Set converter
parameters again if power unit was changed.
F45
Device added (default param.)
Possible cause:
1.
Option board of different type added.
Correcting measures:
1.
Reset
2.
Set the option board parameters again.
F50
4mA supervision
Possible cause:
1.
Current at the analogue input is below 4mA.
2.
Signal source has failed
3.
Control cable is broken or loose
Correcting measures:
1.
Check the current loop circuitry.
F51
External fault
Possible cause:
1.
Digital input fault.
Correcting measures:
1.
Remove fault situation from external device.
F52
Keypad communication
Possible cause:
1.
The connection between the control keypad or NCDrive and the AC drive is broken.
Correcting measures:
1.
Check keypad connection and possible keypad cable.