Arfiff05 Standard AFE-II
vacon •
21
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.1.16
Operation Hours ID1856
Run state hours
5.2.2
Fieldbus monitoring values
V1.2.1
FB Control Word
ID 1160
Control word from fieldbus. Below table is for bypass operation for such fieldbus board that natively
supports this or can be parameterized to bypass mode.
FB Control Word ID1160
Signal
Comment
SM
B00
DC Charge
0= Open MCB.
1= Close DC charge contactor, MCB closed automatically, see
B01.
1,2,3
B01
MCB Close Enable
0=
Disable
Closing
of
MCB
(Also
opens
if
Control
Options.B0=TRUE)
1= Enable Closing of MCB (Works also for reclosing)
3
B02
Quick Stop
0= Quick Stop
1= No Quick Stop
3
B03
Run
0= AFE is stopped
1= AFE is started
1,2,3
B04
Output Power Limit to
Zero
0= Output Power Limit to Zero (7%)
1= Output Power Limit = P2.5.2.1
3
B05
Disable Power Increase.
Input or Output
0= Disable increase of power.
1= Power limits defined by G2.5.2
3
B06
Input Power Limit to
Zero
0= Input Power Limit to Zero (7%)
1= Output Power Limit = P2.5.2.2
3
B07
Reset
0>1 Reset fault.
1,2,3
B08
DC Voltage Ref B00
B00 | B01
0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %
0 | 1 = 110 %
1 | 0 = 115 %
1 | 1 = 120 %
2,3
B09
DC Voltage Ref B01
2,3
B10
Fieldbus Control
0= No control from fieldbus
1=Control from fieldbus
2,3
B11
Watchdog
communication between fieldbus master and the drive.
2,3
B12
FB DIN2
Can be used to control RO or directly parameter by ID number.
G2.4.1
1,2,3
B13
FB DIN3
Can be used to control RO or directly parameter by ID number.
G2.4.1
1,2,3
B14
FB DIN4
Can be used to control RO or directly parameter by ID number.
G2.4.1
1,2,3
B15
Reserved for future use.