4. Periodic Test by Installer Code
78
D-306488 WK250 Installer’s Guide
Option
Instructions
SIRENS TEST
You can test wireless sirens and strobes and sirens of smoke sensors and keypads.
To initiate the siren test press
.
The display now reads "
SIREN N
"
“<NEXT> or
<OK>”
. "
N
" indicates the zone location assigned to the siren that is currently being tested.
First the panel siren sounds for 1 second after which the WP system will automatically
repeat the procedure for the next siren enrolled in the system until all sirens are tested. You
should listen to the sirens sounds and make sure that all sirens sound.
Once all the sirens have been tested, the control panel will now test the sirens of smoke
sensors that are enrolled in the alarm system. The display now reads "
Zxx: SMOKE
SIREN
"
“<NEXT> or <OK>”
, where "
Zxx
" indicates the zone number of the smoke
sensor. During this time, the siren of the tested smoke sensor will sound for 10 seconds.
Press
to test the siren of the next smoke sensor.
Once all the sirens of the smoke sensors have been tested, the control panel will now
test the sirens of keypads that are enrolled in the alarm system. The display now reads
"
Kxx: KEYPAD SIREN
"
“<NEXT> or <OK>”
, where "
Kxx
" indicates the zone number
of the keypad. During this time, the siren of the tested smoke sensor will sound for 10
seconds.
When the sirens test is complete, the display reads "
SIREN TEST ENDED
". Press the
or the
button to confirm the test.
TEMPERATURE TEST
The WK250 reads the temperature of the zone.
To display the temperature of zones on the WK250, press
. The WK250 displays
the temperature, the sensor number and the sensor location, as in the following
example: "
Z01 24.5
°
C
"
"
Z01:Temp. Sensor
" changes to "
Custom
". Repeatedly click
the
button to review the temperature of each zone (by Temperature Sensor).
When the temperature of all zones has been reviewed, the display reads "
DEVICE TEST
ENDED
". Press the
or the
button to confirm the test and then move to the
next step to test the other devices.
TEST ALL DEVICES
You can test all devices in one procedure.
Pressing
during the testing process will display details of each device that has not
yet been tested. The WK250 reads the device number, followed by the device type (for
example, Contact Sensor, Motion Sensor or Keyfob) and followed by the device location. At
this stage, pressing any one of the following keys will open the following options:
1.
Press
to view details of the next untested device.
2.
Press
to exit the test process.
During testing, you can also check the signal strength indication of each device, (for
further details, refer to the device Installation Instructions).
After all devices have been tested, the WK250 reads "
DEVICE TESTS END
".