3. Programming 

22 

D-306488 WK250 Installer’s Guide

 

3.4.5 Replacing a Device 

Use this option to replace a faulty device that is enrolled in the system with another device of the same type number (i.e. 

same first 3 digit of the ID number – see section 3.4.2.A) while keeping the same configuration of the original device. 

There is no need to delete the faulty device or to reconfigure the new device. Once enrolled, the new device will be 

configured automatically to the same configuration of the faulty (replaced) device. 
To 

Replace

, a device proceed as follows: 

Step 1

 

 

Step 2

 

 

Select "REPLACE DEVICES" 

Option 

[1] 

Select the respective device 

Group  

[2] 

 

 

 

 

02:ZONES/DEVICES 

 

 

CONTACT SENSORS 

 

 

 

 

 

 

REPLACE DEVICES 

 

KEYFOBS 

 

 

 

 

 

 

Step 3

 

 

Step 4

 

 

Select exact device you wish to 

replace 

[3] 

Enroll the new device 

[4] 

 

 

 

 

K03:Keyfob 

ID No. 300-0307 

 

ENROLL NOW or 

ENTR ID:300-xxxx 

 

 

 

 

 

 

 

 – Replacing a Device 

[1] 

Enter the 

Installer Menu

, select the "

02:ZONES/DEVICES

" option (see section 3.2) and then select the 

"

REPLACE DEVICES

" option. 

[2] 

Select the respective group of the device you wish to replace. For example, "

KEYFOBS

".  

[3] 

Scroll the Device Group, identify (by zone and/or ID number) the exact device you wish to replace, for 

example: "

K03: Keyfob

 > 

ID No. 300-0307

".  

[4] 

From here on the process is the same as the enrollment process of a new device. To continue, refer to 

section 3.4.2 Part A, Step 2. 
If you try enrolling a new device of a different type than the replaced device, the alarm system will reject the 
new device and the display will read "

WRONG DEV.TYPE

".  

When done, the display shows the device details of the new device. 

Содержание DSC WK250

Страница 1: ...iting the Installer Mode 12 3 3 Setting Installer Codes 12 3 3 1 Identical Installer and Master Installer Codes 14 3 4 Zones Devices 14 3 4 1 General Guidance Zones Devices Menu Options 14 3 4 2 Addin...

Страница 2: ...gramming Access Permission 51 3 6 8 Broadband 53 3 7 PGM Output 54 3 7 1 General Guidance 54 3 7 2 Open Collector States 54 3 7 3 PGM Output Configuration 54 3 7 4 PGM 5 Connection 56 3 7 5 Entering D...

Страница 3: ...Code 77 4 1 General Guidance 77 4 2 Conducting a Periodic Test 77 5 Handling System Troubles 81 6 Reading the Event Log 83 APPENDIX A Specifications 85 APPENDIX B Working with Partitions 86 B1 User I...

Страница 4: ...g any of the installation procedures below remove the unit from its bracket by sliding the unit upward 2 1 Inserting Battery Open the battery cover and insert the 4 batteries according to the illustra...

Страница 5: ...d as illustrated in the following drawing 1 Drill 4 mounting holes 3 Line the two slots of the unit with the two hinges of the bracket and then slide the unit downward on the bracket 2 Position the br...

Страница 6: ...Y DEVICES 3 Enroll the device by pressing the AUX button for about 5 seconds until the LED turns ON and then release the button or enter the 7 digit ID code that appears on the sticker on the back of...

Страница 7: ...taller Mode User Settings and Periodic Test 2 Press the ENROLL button again within the timeout period 10 seconds Any keypad that was enrolled in keypad no 01 is deleted from the system The ENROLL LED...

Страница 8: ...not report a supervision signal at least once within a predefined time a MISSING trouble alert is initiated Therefore if you take the keypad out of the protected premises switch the Supervision OFF to...

Страница 9: ...the WK250 device and then entering the user code or presenting the proximity tag to the tag reader will return the device to normal display see section 3 5 6 Configuring Audible Visual User Interface...

Страница 10: ...Navigation Setting Function NEXT Use to move scroll forward to the next menu options BACK Use to move scroll backward to the previous menu options OK Use to select a menu option or to confirm a settin...

Страница 11: ...n the system is disarmed The process described refers to the case where User permit is not required If User permit is required select the User Settings option and ask the Master User to enter his code...

Страница 12: ...ng the selected parameter the display returns to step 3 To Change the Configuration of the Selected Option When entering the selected option the display shows the default or the previously selected se...

Страница 13: ...Enter NEW Master Installer Installer code or Guard code 3 INSTALLER MODE NEW MASTER CODE 9999 NEW MASTER CODE 9999 ENTER CODE or or NEW INST CODE 8888 NEW INST CODE 8888 or or 01 INSTALL CODES NEW GU...

Страница 14: ...the non Master Installer Code back again in other words undo the change to the temporary code so that the non Master Installer can still enter the system 3 4 Zones Devices 3 4 1 General Guidance Zone...

Страница 15: ...werG devices including Keyfobs cannot be used on more than one system at one time Remember to verify panel and device compatibility 2 See enrollment by button or device ID below If enrollment is succe...

Страница 16: ...he Installer Code or to allow access to the programming menus Remember The system will indicate a NOT NETWORKD trouble until the 2 nd stage of all registered devices is completed Note The Soak Test on...

Страница 17: ...gnals sent from the device Press and select a suitable zone type The list of available Zone Types and the explanation for each zone type is provided below Notes 1 As a shortcut press the 2 digit seria...

Страница 18: ...P8033 Can be customized by 06 CUSTOM NAMES menu see section 3 8 Zone Type List Zone No and Type Description Zxx ZONE TYPE 1 Exit Entry 1 This Zone starts the exit time when the user arms the system or...

Страница 19: ...030 or WP8033 Installer s Guide Figure 3 8b Zxx ZONE TYPE 12 Non Alarm This zone does not create an alarm and is often used for non alarm applications For example a detector used only for sounding a c...

Страница 20: ...he device press the key 4 Del to Delete to step 2 Deleting a Device 1 Enter the Installer Menu select the 02 ZONES DEVICES option see section 3 2 and then select the DELETE DEVICES option 2 Select the...

Страница 21: ...0 ZONE TYPE Z10 SET CHIME Z10 PARTITIONS Z10 DEV SETTINGS Modifying or Reviewing a Device 1 Enter the Installer Menu select the 02 ZONES DEVICES option see section 3 2 and then select the MODIFY DEVIC...

Страница 22: ...DEVICES KEYFOBS Step 3 Step 4 Select exact device you wish to replace 3 Enroll the new device 4 K03 Keyfob ID No 300 0307 ENROLL NOW or ENTR ID 300 xxxx Replacing a Device 1 Enter the Installer Menu...

Страница 23: ...n Sens enable Z09 Motion Sens enable Enabling Soak Test mode 1 Enter the Installer Menu select the 02 ZONES DEVICES option see section 3 2 and then select the ADD TO SOAK TEST option 2 Select the resp...

Страница 24: ...r certain group of devices and then change the defaults for another group IMPORTANT Devices that were already enrolled in the alarm system before the defaults have been changed will not be affected by...

Страница 25: ...vent Counter parameter setting of Motion Sensors enrolled from now on will be high 5 The new default does not affect motions sensors that were already enrolled before the change was made but only new...

Страница 26: ...configurable features and parameters related to the functionality of the Zones 3 5 3 Alarms Troubles Contains configurable features and parameters related to initiating canceling and reporting of Ala...

Страница 27: ...5 01 ENTRY DELAY1 21 SWINGER STOP 31 PANIC ALARM 43 PANEL SIREN 02 ENTRY DELAY2 22 CROSS ZONING 32 DURESS ALARM 44 SIREN TIME 03 EXIT DELAY Continues 33 INACTIVE ALRT 45 STROBE TIME 04 EXIT MODE 34 T...

Страница 28: ...rs and routes without causing an alarm Following entry the user must disarm the WK250 before the entry delay expires Slow rate warning beeps start sounding once the door is opened until the last 10 se...

Страница 29: ...and end by exit Note In some WP variants this menu is displayed in the Operation Mode only 05 QUICK ARM off Define whether or not the user will be allowed to perform quick arming or not Once quick ar...

Страница 30: ...and its configuration settings To select an option and change its configuration refer to section 3 5 1 Option and default Configuration Instructions 21 SWINGER STOP after 1 alarm Define the number of...

Страница 31: ...disabled applicable in UK panels only 32 DURESS ALARM CODE 2580 A duress ambush alarm message can be sent to the Monitoring Station if the user is forced to disarm the system under violence or menace...

Страница 32: ...alarm time a cancel alarm message is sent to the Monitoring Station indicating that the alarm was canceled by the user Previously known as ALARM CANCEL Options not active default in USA in 1 5 15 60...

Страница 33: ...e whether the control panel s built in siren will sound alarms on or remain silent off Options on and off 44 SIREN TIME 4 minutes Define the period of time the sirens will sound upon alarm Previously...

Страница 34: ...mute the warning beeps only when the system is armed HOME The pushbuttons and provide selection of the corresponding partitions Pressing each button repeatedly will toggle between each option When Par...

Страница 35: ...nd will also perform the Fire Emergency function 56 SCREEN SAVER off Certain regulations require that the system status display will not be exposed to unauthorized persons The Screen Saver option when...

Страница 36: ...must be selected To comply with UK Class 6 requirements class 6 30 60 must be selected 62 MISSING REPRT after 12 hours Define the time window for reception of supervision keep alive signals from the v...

Страница 37: ...default in UK 93 SOAK PERIOD disable Define the period of time for the Soak Test Options disable default 7 days 14 days or 21 days Notes 1 If set to one of the above pre defined period of times to be...

Страница 38: ...o Alarm Verification and forwarding of image clips to the Monitoring Station and other remote subscribers via e mail and or MMS network 3 6 6 6 UP DOWNLOAD Contains configurable connection information...

Страница 39: ...TRIES 3 6 4 02 1st RPRT CHAN 47 GSM RETRIES These options are available only to the Master Installer 03 2nd RPRT CHAN 48 BB IP RETRIES 04 3rd RPRT CHAN 51 TEL AUTO TEST 05 DUAL RPRT 52 AUTO TEST TIME...

Страница 40: ...See also Chapter 6 section B 12 in the WK250 User s Guide Private tel 2 SMS tel 2 Private tel 3 SMS tel 3 Private tel 4 SMS tel 4 REDIAL ATTEMPTS VOICE PRIVATE TEL ACKNOWLEDGE 5 MOTION CAMERA IMAGE FO...

Страница 41: ...AND DHCP CLIENT 3 6 8 MANUAL IP RESET MODULE 3 6 2 Configuring PSTN landline phone Connection The WP panel includes a telephone dialer for reporting to Monitoring Stations using several optional Alarm...

Страница 42: ...GPRS module is capable of communicating with the Monitoring station receiver by GPRS GSM Voice analog or SMS Channels Each of the channels can be separately enabled or disabled to allow or prohibit th...

Страница 43: ...d Previously known as FORCE HOME NTWK Options roam disable roam enable GPRS ALWAYS ON disable Define whether the control panel will stay continuously connected enable via GPRS communication or disconn...

Страница 44: ...C S 2 For detailed and more complete explanation see the Event Reporting Chart at the end of this section Options all o c backup all o c o c disable report all all all alrt alrt all backup all o c al...

Страница 45: ...one line to which the system is connected you should refer to the AREA CODE option in section 3 6 2 and act as instructed there Digit Keying Digit Significance A 0 The dialer waits 10 seconds or waits...

Страница 46: ...4 2 1800 2300 Scancom SIA textand Contact ID 46 PSTN RETRIES 4 attempts Define the number of times the system will retry to report to the Monitoring Station in case of failure to report via the PSTN t...

Страница 47: ...ration Mode only 62 RECENT CLOSE rprt disabled False alarms may occur if users do not exit the premises within the exit delay period resulting in a false alarm a short time later In such cases inform...

Страница 48: ...bient Level Select the ambient noise level of the installation If it is a relatively noisy environment set it to High default setting If it is a very quiet environment set to Low voice cs disable ring...

Страница 49: ...o to select which event groups will be reported to each of the two Monitoring Stations The table below describes the available reporting options The minus symbol means but less except e g all alrt mea...

Страница 50: ...clips for verification of Burglary alarms detected by the Motion Cameras The system can be configured to capture image clips also upon occurrence of Non Burglary alarms i e Fire Duress Emergency and P...

Страница 51: ...rammer PC software The PowerManage server calls from a cellular modem to the Panel s SIM card number The panel checks the caller ID and if identical with any of the two callers ID 1 or 2 programmed in...

Страница 52: ...oad functionality via GPRS The functionality is determined through a sub menu of the GPRS UP DOWNLOAD option as shown below To program Press to enter the GPRS UP DOWNLOAD sub menu and then select and...

Страница 53: ...btain an IP address automatically using a DHCP server or to enter an IP address manually Options DHCP DISABLE and DHCP ENABLE MANUAL IP Manually enter LAN parameters IP ADDRESS 192 168 000 200 Enter t...

Страница 54: ...output upon arming Away Options disable turn ON turn OFF and activate PULSE PGM BY ARM HOME disable Activates the PGM output upon arming Home Options disable turn ON turn OFF and activate PULSE PGM B...

Страница 55: ...ions Zone B and Zone C and repeat the above process When done press to return Zone A Z _ _ Zone B Z _ _ Zone C Z _ _ disable Options disable turn ON turn OFF activate PULSE toggle Note If you select t...

Страница 56: ...ONS disable PGM 5 OPTIONS enable PGM 5 OPTIONS enable 3 7 5 Entering Daytime Limits 05 OUTPUS LOCKOUT TIME Enter the LOCKOUT TIME menu and enter the daytime limits through which the PGM device will tu...

Страница 57: ...edit the desired custom location Note WP8010 All 31 custom names can be edited WP8030 WP8033 The following custom names can be edited Dining room Garage door Guest room Master bath Master Bdrm Custom...

Страница 58: ...case letters a b c z and uppercase letters A B C Z 1 a A b B c C 2 Moves the digits cursor from left to right Long press for fast movement d D e E f F 3 Moves the digits cursor from right to left Long...

Страница 59: ...RD A MSG appears momentarily and then changes to TALK NOW 0 A progress indicator will be displayed that is incremented each time by 25 as follows 0 25 50 75 and 100 At the end of the recording process...

Страница 60: ...below which provides you with the options Option and default Instructions VOICE BOX MODE VOICE BOX MIXED Define whether two way voice communication is to be sounded either via the external speakerphon...

Страница 61: ...ests the SIM number to ensure correct entry of the SIM number in the control panel 3 9 4 BROADBAND MODULE Enables to test the communication of the Broadband Module with the PowerManage server 3 9 5 To...

Страница 62: ...in TEST ALL DEVICES press to initiate the test The devices are tested in the following order wall mounted devices vanishing magnetic contact devices keyfobs and panic buttons At the end of the test pr...

Страница 63: ...ss indicated by the corresponding display for example TEST KEYFOBS 01 press any key of the selected handheld device to initiate the test At the end of the test process the WK250 will present the devic...

Страница 64: ...est Upon test completion the WK250 will present the test result The following table presents the test result messages Message Description Unit is OK GSM GPRS is functioning correctly GSM com loss GSM...

Страница 65: ...will display SIM not verified 3 9 5 Testing the Broadband PowerLink Module The Broadband diagnostic procedure enables to test the communication of the Broadband Module see section 3 6 8 with the Powe...

Страница 66: ...DULE RCVR 1 UNREG The WP unit is not registered to IP receiver 1 or 2 BROADBAND MODULE RCVR 2 UNREG BROADBAND MODULE TIMEOUT ERR Broadband Module does not respond to test result within 70 sec BROADBAN...

Страница 67: ...on 3 2 2 Select leave KP250 to reset factory default parameters or press and select del all devices to delete all devices in the system 3 Press to confirm 4 Enter the Installer Code 9999 by default No...

Страница 68: ...2 Control panel software version LCD CAT SN JS700421 v1 0 02 Control Panel keypad software version 1 PANEL ID 100005 Control panel ID for PowerManage connectivity PYTHON VERSION FFFFFFFF GSM image tra...

Страница 69: ...e feature is applicable only in specific WP variants 3 14 1 General Guidance Operation Mode Menu This mode allows you to select an operation mode for the control panel according to specific compliance...

Страница 70: ...s been activated until the control panel is disarmed DD243 An alarm initiated by another detector during the entry delay is not regarded as a confirmed alarm normal mode The control panel will report...

Страница 71: ...te via 2 specific doors and routes without causing an alarm Following entry the user must disarm the control panel before the entry delay expires Slow rate warning beeps start sounding once the door i...

Страница 72: ...he confirmation time There are no alarm restrictions during entry delay or for the delay zone 03 END EXIT MODE fob timer Define how the exit delay is terminated or restarted according to the following...

Страница 73: ...must disarm the control panel before the entry delay expires Slow rate warning beeps start sounding once the door is opened until the last 10 seconds of the delay during which the beeping rate increa...

Страница 74: ...sing the AUX button on the keyfob 1 or when the exit delay has expired whichever first restart reentry Exit delay restarts when the door is reopened during exit delay The restart occurs once only Rest...

Страница 75: ...n 4 hours 12 CNCEL ANOUNCE enable Define whether a special beep will sound when an alarm cancel event is sent to the monitoring station Options enable and disable 13 ABORT ANOUNCE enable Define that w...

Страница 76: ...a confirmed alarm enable The system will report a confirmed alarm 08 ENTRY DELAY 1 30 seconds Two different entry delays allow the user to enter the protected site while the system is in the armed sta...

Страница 77: ...d devices the WK250 will read OK TO END You can now do one of the following press to abort the testing procedure press to continue the testing procedure or press to exit the testing procedure 4 2 Cond...

Страница 78: ...his time the siren of the tested smoke sensor will sound for 10 seconds When the sirens test is complete the display reads SIREN TEST ENDED Press the or the button to confirm the test TEMPERATURE TEST...

Страница 79: ...he TEST ONE DEVICE sub menu and use to navigate to MOTION SENSORS 2 Press the following screens will appear Z01 Motion Sens location 3 Press continuously to select a different zone number 4 Press If t...

Страница 80: ...wever since there are various models of the shock detector not all of these screens will appear on some models 5 At this stage activate each input of the shock detector in turn To test motion detector...

Страница 81: ...to the monitoring station or to a private telephone or a message was sent but was not acknowledged 1 Check telephone cable connection 2 Check that correct telephone number has been dialed 3 Dial Moni...

Страница 82: ...e and connected to the device 2 Replace the device battery MISSING A device or detector has not reported for some time to the control panel 1 Make sure the device is physically present 2 Check the dis...

Страница 83: ...event log that can be reviewed via the Remote Programmer PC software application or by the remote PowerManage server When reading the event log events are shown in chronological order from the newest...

Страница 84: ...st of events Erasing and Exiting the Event Log 5 From anywhere within the event log press the button and then press 6 At this stage in the procedure clicking the button will take you to OK TO EXIT wit...

Страница 85: ...3 years for typical use Low Battery Threshold 3 8 V Power source Battery 4 8VDC 6VDC Back light Blue keypad white display Operating Temperature 0 C to 55 C 32 F to 131 F Humidity Average relative humi...

Страница 86: ...e or zones to 2 or 3 partitions Table A1 summarizes the behavior of the different zone types in a common area Table A1 Common Area Definitions Common area zone types Definition Perimeter Acts as defin...

Страница 87: ...s Definition Gas Temperature 24 hour silent 24 hour audible Non alarm Note A Soak Test of Common areas cannot be initiated when one of its partitions is armed When Soak Test of a Common area is active...

Страница 88: ...ote Your installer will never designate a 24 hour zone or a fire zone as a chime zone because both zone types actuate an alarm if disturbed while the system is in the disarmed state Although one zone...

Страница 89: ...larm signal and various other status signals to the control panel After transmission it stands by to sense further motion Non Alarm Zone Your installer can designate a zone for roles other than alarm...

Страница 90: ...t to the desired zone Since the zone is distinguished by number and name the control panel can report the zone status to the user and register in its memory all the events reported by the zone detecto...

Страница 91: ...al Les antennes utilis es pour ce produit ne doivent pas tre situ s ou exploit s conjointement avec une autre antenne ou transmetteur WARNING To comply with FCC and IC RF exposure compliance requireme...

Страница 92: ...credited or replaced at DSC s option Products not covered by this warranty or otherwise out of warranty due to age misuse or damage shall be evaluated and a repair estimate shall be provided No repair...

Отзывы: