6.0 Options
- 75 -
6.1.7 SG-CPM5 Options: [6XX] and [7XX] - Troubles
The following sections control the display of trouble conditions. For installations that do not have a full SG-System 5 configuration, selected troubles
can be disabled. Disabled troubles do not display.
Option [601]: CPM5 1 Fan Trouble
Default (Enabled)
This option is used to enable or disable SG-CPM5 1 fan supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [602]: CPM5 2 Fan Trouble
Default (Enabled)
This option is used to enable or disable SG-CPM5 2 fan supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [603]: PSU5 1 Trouble
Default (Enabled)
This option is used to enable or disable SG- PSU5 1 supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [604]: PSU5 2 Trouble
Default (Enabled)
This option is used to enable or disable SG- PSU5 2 supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [605]: Fan Tray 1 Trouble
Default (Enabled)
This option is used to enable or disable fan tray 1 supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
Option [606]: Fan Tray 2 Trouble
Default (Enabled)
This option is used to enable or disable fan tray 2 supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
Option [607]: Fan Tray 3 Trouble
Default (Enabled)
This option is used to enable or disable fan tray 3 supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
Option [608]: Fan Tray 4 Trouble
Default (Enabled)
This option is used to enable or disable fan tray 4 supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
Option [609]: UPS AC 1 Trouble
Default (Disabled)
This option is used to enable or disable UPS AC 1 input supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [610]: UPS AC 2 Trouble
Default (Disabled)
This option is used to enable or disable UPS AC 2 input supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
S
G
-S
ys
te
m
5
O
pe
ra
ti
ng
M
anua
l
Содержание SG-System 5
Страница 68: ...6 0 Options 68 Automation Mode Diagrams FIGURE 6 1 Flow Diagram for Loop Mode 0 SG System 5 Operating Manual ...
Страница 69: ...6 0 Options 69 FIGURE 6 2 Flow Diagram for Fallback Mode 1 SG System 5 Operating Manual ...
Страница 70: ...6 0 Options 70 FIGURE 6 3 Flow Diagram for All Mode 2 SG System 5 Operating Manual ...
Страница 71: ...6 0 Options 71 FIGURE 6 4 Flow Diagram for IP Fallback Mode 3 SG System 5 Operating Manual ...