6.0 Options
- 67 -
Option [401]: Automation Mode
Default Auto IP Fallback(4)
The TCP/IP connection is the primary output of automation alarms. Sockets appear and disappear as processes are terminated and initiated. After socket
loss, automation output is redirected to other connections. This option controls how output is redirected if a connection fails.
NOTE: The unit must be reset before parameter changes take effect.
Loop (0)
The active SG-CPM5 uses TCP/IP at start-up. The unit automatically loops between TCP/IP and serial if failure is detected. If neither TCP/IP nor serial
are present, the SG-CPM5 switches to Manual mode. In Manual mode, the standby SG-CPM5 only takes over if the active/manual SG-CPM5 fails or
is rebooted
Fallback (1)
If both outputs are present, the active SG-CPM5 uses TCP/IP until it fails then switches to serial. The SG-CPM5 does not switch back to TCP/IP mode
until a reset fallback command is received from the console. If neither TCP/IP nor serial are present, the SG-CPM5 switches to manual mode. In
manual mode, the standby SG-CPM5 only takes over if the active/manual SG-CPM5 fails or is rebooted.
All Mode (2)
The active SG-CPM5 always sends to all connected outputs. If at least one output replies with an ACK, the alarm is considered to be transmitted,
whether the other output acknowledged it or not. This setting is NOT recommended. If neither TCP/IP nor serial are present, the SG-CPM5 switches to
manual mode. In manual mode, the standby SG-CPM5 only takes over if the active/manual SG-CPM5 fails or is rebooted.
IP Fallback Mode (3)
At start-up, the primary SG-CPM5 sends through the TCP/IP output.
If the primary SG-CPM5 TCP/IP output fails, the secondary SG-CPM5 sends through the TCP/IP output.
If the secondary SG-CPM5 TCP/IP output fails, the primary SG-CPM5 sends through its serial output.
If the primary SG-CPM5 serial fails, the secondary SG-CPM5 sends through the serial output.
If neither TCP/IP nor serial are present, the SG-CPM5 switches to manual mode.
The SG-CPM5 does not switch back to TCP/IP mode until a reset fallback command is received from the console or the serial fails.
Automatic IP Fallback (4)
This mode is similar to Fallback except that when the TCP/IP connection is restored, the SG-CPM5 automatically returns to the TCP/IP output to send
events. This eliminates the need for a reset fallback command from the console.
S
G
-S
ys
te
m
5
O
pe
ra
ti
ng
M
anua
l
Содержание SG-System 5
Страница 68: ...6 0 Options 68 Automation Mode Diagrams FIGURE 6 1 Flow Diagram for Loop Mode 0 SG System 5 Operating Manual ...
Страница 69: ...6 0 Options 69 FIGURE 6 2 Flow Diagram for Fallback Mode 1 SG System 5 Operating Manual ...
Страница 70: ...6 0 Options 70 FIGURE 6 3 Flow Diagram for All Mode 2 SG System 5 Operating Manual ...
Страница 71: ...6 0 Options 71 FIGURE 6 4 Flow Diagram for IP Fallback Mode 3 SG System 5 Operating Manual ...