6.0 Options
- 74 -
trouble status on the SG-System 5 is not affected. The receiver console time update function must be disabled when using this feature to ensure that the
SG-CPM5 remains synchronized with the automation PC.
Printer message: "Time&Date Update Fail"
Automation message: 0RRLLL[#0000¦NRU0000]
Option [450]: Visual Verification Automation TCP Port
Default (2025)
This section sets the visual verification automation TCP port. The visual verification automation TCP port is the port that automation or the SG-Systems
Console connects to.
6.1.6 SG-CPM5 Options: [5XX] - Printer Options
Option [501]: Printer Mode
Default (Loop)
Printer outputs can be configured in a similar manner to automation outputs except that the only acceptable values are either LOOP (00) or ALL (02).
Setting the printer mode to ALL transmits the printer message to all active ports. The first acknowledgment received is used to process the next printer
message. Setting the Printer Mode to LOOP operates similar to the Automation mode LOOP, whereas it outputs to TCP/IP. If TCP/IP fails, it outputs
to Serial. If Serial fails, it outputs to TCP/IP, etc.
NOTE: Order of sequence is TCP then serial. Sur-Gard does NOT recommend changing the default setting unless using more than one
printer.
NOTE: The unit must be reset before parameter changes take effect.
Option [502]: Serial Printer 1 Format
Default (Disabled)
This section enables the serial handshake protocol that the SG-CPM5 uses to send signals to the device (printer or terminal) connected to the serial
printer port.
NOTE: The unit must be reset before parameter changes take effect.
Option [503]: Serial Printer 1 Baud Rate
Default (57600)
Determines the baud rate at which the SG-CPM5 communicates to the serial printer connected on serial printer port 1.
Valid entries are: 1200, 2400, 4800, 9600, 19200, 38400, or 57600.
NOTE: The unit must be reset before parameter changes take effect.
Option [504]: Serial Printer 1 Data Bits
Default (8)
Determines the number of data bits used to communicate to the serial printer on serial printer port 1. Choose 7 or 8 data bits.
NOTE: The unit must be reset before parameter changes take effect.
Option [505]: Serial Printer 1 Parity
Default (0)
Determines the parity of serial printer port 1
Numeric Setting Display
Description
0
none no parity (default)
1
odd
odd parity
2
even
even parity
NOTE: The number of stop bits cannot is fixed at 2.
NOTE: The unit must be reset before parameter changes take effect.
S
G
-S
ys
te
m
5
O
pe
ra
ti
ng
M
anua
l
Содержание SG-System 5
Страница 68: ...6 0 Options 68 Automation Mode Diagrams FIGURE 6 1 Flow Diagram for Loop Mode 0 SG System 5 Operating Manual ...
Страница 69: ...6 0 Options 69 FIGURE 6 2 Flow Diagram for Fallback Mode 1 SG System 5 Operating Manual ...
Страница 70: ...6 0 Options 70 FIGURE 6 3 Flow Diagram for All Mode 2 SG System 5 Operating Manual ...
Страница 71: ...6 0 Options 71 FIGURE 6 4 Flow Diagram for IP Fallback Mode 3 SG System 5 Operating Manual ...