4.0 Hardware Descriptions and Specifications
- 30 -
4.2.7 UPS Setup
FIGURE 4-8: SG-System 5 UPS Supervision Connection Diagram
UPS LOW BAT Normally Closed
Common
UPS AC TROUBLE Normally Closed
UPS
AC In
AC Out
Input 2
Input 1
COM
IEC Power
Connector
EGND
FIGURE 4-9: I/O Terminal UPS connections
1
3
2
1.
Input 1
UPS AC Failure: Toggles from ground to open on failure.
2.
GND
Common (ground)
3.
Input 2
UPS DC Failure: Battery of the UPS failed (toggles from ground to open on failure)
For UL/ULC installations, use a UL listed UPS (Uninterruptible Power Supply) for protective-signaling systems and/or a listed burglary alarm power
supply, as applicable.
NOTE: UPS connection is to be made using dry contact connections provided by the UPS.
For UL and ULC installation of model SG-System 5: UPS Output 120V AC/60Hz, 5A
For ULC Installations, the equipment shall be rack mounted and energized by a permanently wired supply in accordance with C22.1, Canadian Elec-
trical Code, Part 1, Safety Standard for Electrical Installations, section 32.
Connection to a UPS (Uninterruptible Power Supply) with minimum 24 hour standby capability is required.
WARNING:
To reduce the risk of electrical shock, the product is provided with a grounding type power supply IEC receptacle. Connect product
using an appropriate IEC cable to a grounded receptacle.
S
G
-S
ys
te
m
5
O
pe
ra
ti
ng
M
anua
l
Содержание SG-System 5
Страница 68: ...6 0 Options 68 Automation Mode Diagrams FIGURE 6 1 Flow Diagram for Loop Mode 0 SG System 5 Operating Manual ...
Страница 69: ...6 0 Options 69 FIGURE 6 2 Flow Diagram for Fallback Mode 1 SG System 5 Operating Manual ...
Страница 70: ...6 0 Options 70 FIGURE 6 3 Flow Diagram for All Mode 2 SG System 5 Operating Manual ...
Страница 71: ...6 0 Options 71 FIGURE 6 4 Flow Diagram for IP Fallback Mode 3 SG System 5 Operating Manual ...