Quick Reference Guide
Hardware
Toshiba VP 300 System Specifications
Electrical Requirements
120 VAC System
Voltage Range
90–132 VAC
Frequency
47–63 Hz
Maximum Power
1,000 Watts
240 VAC System
Voltage Range
180–260 VAC
Frequency
47–63 Hz
Maximum Power
1,000 Watts
-48 VDC System
Voltage Range
42–60 VDC
Maximum Power
1,000 Watts
Remote Alarm
Alarm Relay
Closures
2 (major, minor)
Rating
0.5A at 48 VDC
Access
Rear, DB9 connector
Alarm Callout
Automatic Callout to configurable service number
Alarm Types
Major Alarm
Minor Alarm
Temperature Alarm
Alarm Temperature
< 50F or > 122F
(< 10C or > 50C)
Environmental Requirements
Temperature
Operating (Sea Level)
50F (10C) to 104F (40C)
Non-operating
-50F (-10C) to 129F (54C)
Gradient, operating
50F (10C) per hour, maximum
Gradient, non-operating
68F (20C) per hour, maximum
Humidity
Operating
20–80%, non-condensing
Atmosphere
Particulate Matter (max)
80 micrograms per cubic millimeter
Corrosive Gasses
< 10 ppm
Altitude
Operating:
-200 feet to 10,000 feet
(-61 meters to 3,048 meters)
Non-operating, transit:
-200 feet to 40,000 feet
(-61 meters to 12,192 meters)
Non-operating, storage:
-200 feet to 10,000 feet
(-61 meters to 3,048 meters)
Toshiba VP Systems Release 7.1 July, 1994
Содержание VP 300
Страница 2: ......
Страница 10: ......
Страница 14: ......
Страница 19: ...Quick Reference Guide Hardware Toshiba VP 300 System Specifications Toshiba VP Systems Release 7 1 July 1994 ...
Страница 20: ...Toshiba VP Systems Release 7 1 July 1994 ...
Страница 52: ...Toshiba VP Systems Release 6 1 February 1993 2 14 Installation and Maintenance Manual ...
Страница 56: ...Toshiba VP Systems Release 7 1 July 1994 ...
Страница 146: ......
Страница 312: ...Toshiba VP Systems Release 7 1 July 1994 ...
Страница 314: ......
Страница 444: ......
Страница 496: ......
Страница 542: ......
Страница 598: ...Toshiba VP Systems Release 6 1 February 1993 ...
Страница 600: ...Toshiba VP Systems Release 6 1 February 1993 ...