Relay and protection scheme setting sheet
User
NO-ARC,NO-FD
1CB-ARC,NO-FD
2CB-ARC,NO-FD
1CB-ARC,FD
2CB-ARC,FD
1CB-ARC,NO-FD
Setting
5A rating
1A rating
Relay model
101
102
201
202
203
301
302
303
401
501
204
205
206
196 DEF
DEFFI
0.5 - 5.0
0.10 - 1.00
A Directional earth fault element
1.0 / 0.20
1.0 / 0.20
197
DEFFV
1.7 - 21.0
V ditto
2.0
2.0
198
DEFRI
0.5 - 5.0
0.10 - 1.00
A ditto
1.0 / 0.20
1.0 / 0.20
199
DEFRV
1.7 - 21.0
V ditto
2.0
2.0
200
DEF
θ
0 - 90
deg ditto
85
85
201 DEF
TDEF
0.00 - 10.00
s
Forward definite timer
3.00
3.00
202 BU-trip
TDER
0.00 - 10.00
s
Reverse definite timer
3.00
3.00
203
OC
OC
0.5 - 100.0
0.1 - 20.0
A OC element
6.0 / 1.2
6.0 / 1.2
204
TOC
0.00 - 10.00
s
ditto
3.00
3.00
205
OCI
OCI
0.5 - 25.0
0.10 - 5.00
A IDMT OC element
1.0 / 0.20
1.0 / 0.20
206
TOCI
0.05 - 1.00
-
ditto
0.50
0.50
207
TOCIR
0.0 - 10.0
s
OC definite time reset delay
0.0
0.0
208
EF
EF
0.5 - 5.0
0.10 - 1.00
A Earth fault OC element
1.0 / 0.20
1.0 / 0.20
209
TEF
0.00 - 10.00
s
ditto
3.00
3.00
210
EFI
EFI
0.5 - 5.0
0.10 - 1.00
A IDMT earth fault OC element
1.0 / 0.20
1.0 / 0.20
211
TEFI
0.05 - 1.00
-
ditto
0.50
0.50
212
TEFIR
0.0 - 10.0
s
EF definite time reset delay
0.0
0.0
213
EFL
0.5 - 5.0
0.10 - 1.00
A EF element for ZG fail safe
1.0 / 0.20
1.0 / 0.20
214 UVC
UVCV
10 - 60
V
48
48
215
UVCZ
0.0 - 50.0
0.0 - 250.0
Ω
2.0 / 10.0
2.0 / 10.0
216
UVC
θ
45 - 90
deg
85
85
217
UVCKrs
0 - 1000
%
-- (Linked with Krs of ZG)
-- (Linked with Krs of ZG)
218
UVCKxs
0 - 1000
%
-- (Linked with Kxs of ZG)
-- (Linked with Kxs of ZG)
219
OVG
20 (fixed)
V OV element
--
--
220
UVFS
50 - 100
V UV ph-ph element
88
88
221
UVLS
50 - 100
V UV ph-ph element "L" level
77
77
222
UVFG
10 - 60
V UV ph-g element
51
51
223
UVLG
10 - 60
V UV ph-g element "L" level
45
45
224
UVPWI
30 (fixed)
V UV for positive weak infeed
--
--
225
OCDP
0.5 - 10.0
0.1 - 2.0
A
Curr. change detector for fault under
PSB
4.0 / 0.8
4.0 / 0.8
226 OVS
OVS1
5.0 - 150.0
V OVS1 element
120.0
120.0
227
TOS1I
0.05 - 100.00
-
OVS1 IDMT timer
10.00
10.00
228
TOS1
0.00 - 300.00
s
OVS1 definite timer
0.10
0.10
229
TOS1R
0.0 - 300.0
s
OVS1 definite time reset delay
0.0
0.0
230
OS1DP
10 - 98
% OVS1 DO/PU ratio
95
95
231
OVS2
5.0 - 150.0
V OVS2 element
140.0
140.0
232
TOS2
0.00 - 300.00
s
OVS2 definite timer
0.10
0.10
233
OS2DP
10 - 98
% OVS2 DO/PU ratio
95
95
234 OVG
OVG1
5.0 - 150.0
V OVG1 element
70.0
70.0
235
TOG1I
0.05 - 100.00
-
OVG1 IDMT timer
10.00
10.00
236
TOG1
0.00 - 300.00
s
OVG1 definite timer
0.10
0.10
237
TOG1R
0.0 - 300.0
s
OVG1 definite time reset delay
0.0
0.0
238
OG1DP
10 - 98
% OVG1 DO/PU ratio
95
95
239
OVG2
5.0 - 150.0
V OVG2 element
80.0
80.0
240
TOG2
0.00 - 300.00
s
OVG2 definite timer
0.10
0.10
241
OG2DP
10 - 98
% OVG2 DO/PU ratio
95
95
242 UVS
UVS1
5.0 - 150.0
V UVS1 element
60.0
60.0
243
TUS1I
0.05 - 100.00
-
UVS1 IDMT timer
10.00
10.00
244
TUS1
0.00 - 300.00
s
UVS1 definite timer
0.10
0.10
245
TUS1R
0.0 - 300.0
s
UVS1 definite time reset delay
0.0
0.0
246
UVS2
5.0 - 150.0
V UVS2 element
40.0
40.0
247
TUS2
0.00 - 300.00
s
UVS2 definite timer
0.10
0.10
248
VSBLK
5.0 - 20.0
V UVS blocking threshold
10.0
10.0
249 UVG
UVG1
5.0 - 150.0
V UVG1 element
35.0
35.0
250
TUG1I
0.05 - 100.00
-
UVG1 IDMT timer
10.00
10.00
251
TUG1
0.00 - 300.00
s
UVG1 definite timer
0.10
0.10
252
TUG1R
0.0 - 300.0
s
UVG1 definite time reset delay
0.0
0.0
253
UVG2
5.0 - 150.0
V UVG2 element
25.0
25.0
254
TUG2
0.00 - 300.00
s
UVG2 definite timer
0.10
0.10
255
VGBLK
5.0 - 20.0
V UVG blocking threshold
10.0
10.0
256 BCD
BCD
0.10 - 1.00
-
Broken conductor threshold
0.20
0.20
257
TBCD
0.00 - 300.00
s
BCD definite timer
1.00
1.00
258 Thermal
THM
2.0 - 10.0
0.40 - 2.00
A Thermal overload setting
5.0 / 1.00
5.0 / 1.00
259
THMIP
0.0 - 5.0
0.00 - 1.00
A Prior load setting
0.0 / 0.00
0.0 / 0.00
260
TTHM
0.5 - 300.0
min Thermal Time Constant
10.0
10.0
261
THMA
50 - 99
% Thermal alarm setting
80
80
262
DOCNI
4.0 (fixed)
0.8 (fixed)
A
--
--
263
DOCNV
V
--
--
DOCN
Negative OC relay
6 (fixed)
Undervoltage element with current
compensation
№
Name
Default Setting of Relay Series(5A rating / 1A rating)
Range
Units
Contents
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......