130
⎯
6 F 2 S 0 8 4 6
Requirement Default
setting
Reclose requirement
[R.F-ST.REQ] = CONSTANT_0
(No used)
Reclose start requirement
"SPAR"
[SPR.F2-REQ] = CONSTANT_0
(No used)
"TPAR"
[TPR.F2-REQ] = CONSTANT_0
(No used)
Figure 2.6.2.8 shows the energizing control scheme of the two circuit breakers in the three-phase
autoreclose. OVB and UVB are the overvoltage and undervoltage detectors of busbar voltage VB
in Figure 2.6.2.6. OVL1 and UVL1 are likewise the overvoltage and undervoltage detectors of line
voltage VL1.
OVL2 and UVL2 are likewise the overvoltage and undervoltage detectors of line voltage VL2.
VL2 in the center breaker is equivalent to the busbar voltage VB in the busbar breaker.
SYN1 and SYN2 are the synchronism check elements to check synchronization between the two
sides of the busbar and center breakers, respectively.
TPARL-SET is a scheme signal whose logical level becomes 1 when a three-phase autoreclose
command is output to the lead breaker. SYN-OP is a voltage and synchronism check output.
&
SYN2
UVL2
OVL2
UVL1
OVL1
SYN1
UVB
OVB
TLBD1
0.01 – 1.00s
TDBL1
0.01 – 1.00s
0.01 – 10.00s
0.01 – 1.00s
0.01 – 1.00s
0.01 – 10.00s
≥
1
≥
1
&
&
&
&
&
&
&
1
&
&
TSYN1
≥
1
≥
1
"
ONE
"
"
L1
"
"
L2
"
"
01
"
"
02
"
[ARC-CB]
TPARL-SET
+
≥
1
&
&
TLBD2
TDBL2
TSYN2
1
&
&
&
+
[VCHK]
"
LB2
"
"
LB1
"
"
DB
"
"
SY
"
"
OFF
"
SYN
-OP
86
87
89
90
88
273
91
92
93
T3PLL
0.01 – 1.00S
397
3PLL
(Three phase live
line)
Note :
[ARC-CB]
is set to "
ONE
" only when the relay is applied to one-breaker system. Trip and reclose
commands are output only for CB1(bus CB).
Figure 2.6.2.8 Energizing Control Scheme for Two Circuit Breakers
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......