A decision to operate is made 6 times in each power frequency cycle using the above-mentioned
equation. The reactance element operates when two consecutive measurements are made if the
distance to a fault is within 90% of the reach setting. If the distance to a fault is more than 90%, the
reactance element operates when four consecutive measurements are made.
This decision method prevents transient overreaching occurring for faults close to the element
boundary.
Figure 2.5.1.8 Reactance Element
The setting of
θ
1(Z1
θ
1) and
θ
2(Z1
θ
2) are set to the following:
Z1
θ
2 < tan
-1
( X / R
F
)
Where,
X = reactance component
R
F
= fault resistance
Z1
θ
1 < tan
-1
{I
Lmax
/ (I
Lmax
+ I
Fmin
)}
I
Lmax
= maximum load current
I
Fmin
= minimum fault current
Blinder element
The blinder element is commonly applicable to Z1, Z1X, Z2, ZF, Z3, ZR1, ZR2 and Z4. As shown
in Figure 2.5.1.9, the blinder element provides the forward blinder and the reverse blinder. The
operating area of the forward blinder is the zone enclosed by the lines BFR and BFL, and that of
the reverse blinder is the zone enclosed by the lines BRR and BRL. The BFR has an angle
θ
of 75
°
to the R-axis and BFL 90
°
to 135
°
. The angle of BRL is linked with that of BFL.
(a) Forward blinder
(b) Reverse blinder
BRL
R
X
-Rs
θ
75
°
BRR
X
R
θ
75
°
BFR
BFL
R
Rs
X
Rs
Figure 2.5.1.9 Blinder element
(b) Z2 and ZF
X
R
90
°
(a) Z1 and Z1X
θ
2
R
θ
1
X
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......