249
⎯
6 F 2 S 0 8 4 6
Set [WKIT] and [ECHO] to "On" and apply a weak-infeed fault. Check that instantaneous tripping
is performed.
De-energize the binary input BI4 and apply a zone 2 fault. Check that POP tripping does not occur.
Apply a zone 2 fault, and check that binary output relay BO13 operates.
Set the scheme switch [ECHO] to "On".
De-energize the binary inputs BI1, BI2 and BI3 to simulate the breaker being open.
Check that binary output relay BO13 operates when the binary input BI4 is energized.
Apply a zone 4 fault (reverse fault) while the binary inputs BI1, BI2 and BI3 are energized, and
check that the binary output relay BO13 does not operate when the binary input BI4 is energized.
Check that the indications and recordings are correct.
UOP tripping
Set the scheme switch [SCHEME] to "UOP", [WKIT] and [ECHO] to "Off".
De-energize the binary input BI4 to simulate interruption of a trip block signal reception and apply
a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Set [WKIT] and [ECHO] to "On" and apply a weak-infeed fault. Check that instantaneous tripping
is performed.
Energize the binary input BI14 to simulate trip block signal reception and apply a zone 2 fault.
Check that UOP tripping does not occur.
Check that binary output relay BO13 operates in the normal condition.
Apply a zone 2 fault, and check that the BO13 resets.
Set the scheme switch [ECHO] to "On".
De-energize the binary inputs BI1, BI2 and BI3 to simulate the breaker being open.
Check that binary output relay BO13 resets when the binary input BI4 is de-energized.
Apply a zone 4 fault (reverse fault) while the binary inputs BI1, BI2 and BI3 are energized, and
check that the binary output relay BO13 remains operated when the binary input BI4 is
de-energized.
Check that the indications and recordings are correct.
BOP tripping
Set the scheme switch [SCHEME] to "BOP".
Check that the binary input BI4 is de-energized and apply a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Energize the binary input BI4 to simulate trip block signal reception and apply a zone 2 fault.
Check that BOP tripping does not occur.
Apply a zone 2 fault, and check that binary output relay BO13 does not operate. Apply a zone 4
fault (reverse fault), and check that BO13 operates.
Check that the indications and recordings are correct.
SOTF tripping
SOTF tripping is carried out by distance measuring element Z1 to Z4 operation or overcurrent
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......