261
⎯
6 F 2 S 0 8 4 6
(*) This panel is attached only to models assembled in the type B case.
•
Detach the module holding bar by unscrewing the binding screw located on the left side of the
bar.
•
Unplug the ribbon cable running among the modules by nipping the catch (in case of black
connector) and by pushing the catch outside (in case of gray connector) on the connector.
•
Pull out the module by pulling up or down at the top and bottom levers.
•
Insert the replacement module in the reverse procedure.
•
After replacing the SPM module, input the user setting values again.
6.7.4 Resumption of Service
After replacing the failed module or repairing failed external circuits, take the following
procedures to restore the relay to service.
•
Switch on the DC power supply and confirm that the "IN SERVICE" green LED is lit and the
"ALARM" red LED is not lit.
Note:
Supply DC power after checking that all the modules are in their original positions and the
ribbon cables are plugged in.
•
If the telecommunication circuit was repaired, perform a "Manual test" and check that the
circuit is normal. For the "Manual test", refer to Section 4.2.7.2.
•
Supply the AC inputs and reconnect the trip outputs.
6.7.5 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC Standard
60255-6 the storage temperature should be
−
25
°
C to +70
°
C, but the temperature of 0
°
C to +40
°
C
is recommended for long-term storage.
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......