33
⎯
6 F 2 S 0 8 4 6
Element Range
Step
Default
Remarks
(0.1 – 500.0
Ω
0.1
Ω
50.0
Ω
)
BNDG
0.10 - 20.00
Ω
0.01
Ω
12.00
Ω
ZNDG blinder reach
(0.5 - 100.0
Ω
0.1
Ω
60.0
Ω
)
Krs
0 - 1000 %
1%
340%
Residual current compensation = R0/R1
Kxs
0 - 1000 %
1%
340%
Residual current compensation = X0/X1
Krm
0 - 1000 %
1%
300%
Mutual coupling compensation = ROM/R1
Kxm
0 - 1000 %
1%
300%
Mutual coupling compensation = XOM/X1
KrsR
0 - 1000 %
1%
100%
Residual current compensation for ZR = R0/R1
KxsR
0 - 1000 %
1%
100%
Residual current compensation for ZR = X0/X1
TZ1G
0.00 - 10.00 s
0.01 s
0.00 s
Zone 1 timer
TZ2G
0.00 - 10.00 s
0.01 s
0.30 s
Zone 2 timer
TZFG
0.00 - 10.00 s
0.01 s
0.35 s
Zone F timer
TZ3G
0.00 - 10.00 s
0.01 s
0.40 s
Zone 3 timer
TZR1G
0.00 - 10.00 s
0.01 s
0.50 s
Zone R1 timer
TZR2G
0.00 - 10.00 s
0.01 s
0.60 s
Zone R2 timer
TZNDG
0.00 - 10.00 s
0.01 s
0.70 s
Zone ND timer
UVC
Phase selection element
UVCV
10 - 60 V
1 V
48 V
Voltage setting
UVCZ
0.0 - 50.0
Ω
0.1
Ω
2.0
Ω
Reach setting
(0 - 250
Ω
1
Ω
10
Ω
)
UVC
θ
45° - 90°
1°
85°
Characteristic angle
EFL
0.5 – 5.0 A
0.1 A
1.0 A
Earth fault detection
(0.10 – 1.00 A
0.01 A
0.20 A)
UVPWI
30 V fixed
UV for positive weak infeed
Scheme switch
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/
BOP/POP+DEF/UOP+DEF/
BOP+DEF/PUP+DEF
POP
Scheme
selection
CRSCM OFF/ON
ON Telecommunication
service
BLZONE
COM/IND
COM
Common or independent setting for blinder
Z1CNT
1/2/3/4/5
1 (*4)
Zone 1 trip mode selection
PSB - Z1
OFF/ON
ON
Z1 power swing blocking
PSB - Z2
OFF/ON
ON
Z2 power swing blocking
PSB - Z3
OFF/ON
OFF
Z3 power swing blocking
PSB - ZF
OFF/ON
OFF
ZF power swing blocking
PSB - ZR1
OFF/ON
OFF
ZR1 power swing blocking
PSB - ZR2
OFF/ON
OFF
ZR2 power swing blocking
ZFBT
OFF/ON
OFF
ZF backup tripping
ZR1BT
OFF/ON
OFF
ZR1 backup tripping
ZR2BT
OFF/ON
OFF
ZR2 backup tripping
ZNDBT
OFF/ON
OFF
ND zone backup tripping
UVPWIEN
OFF/ON
OFF
Countermeasures for overreaching of a
leading-phase distance element at positive phase
weak infeed condition
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the case
of 5 A rating.
(*2) Valid only when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid only when quadrilateral characteristic is selected by ZS-C and ZG-C.
(*4) Default setting is “5” in the case of models 101 and 102. In other models, the default setting is “1”.
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......