2.5.9 Level
Detectors
In addition to those explained above, GRZ100 has overcurrent, overvoltage, and undervoltage
level detectors described below.
All level detectors except for undervoltage level detectors UVFS and UVFG, and overcurrent
level detector OCBF which require high-speed operation, operate in a similar manner.
That is, the operation decision is made by comparing the current or voltage amplitude with the
relevant setting.
Overcurrent detector OCH and OC
This detector measures A, B, and C phase currents and its sensitivity can be set. The detector OCH
is commonly used for the SOTF and stub protection. The detector OC is commonly used for
backup protection.
Residual overcurrent detector EF and EFL
This detector measures a residual current and its sensitivity can be set. The EF is used for backup
protection. The EFL is used for the earth fault detection of distance protection and VT failure
supervision.
Overvoltage detector OVS1/OVS2/OVG1/OVG2 and undervoltage detector UVS1/UVS2/UVG1/UVG2
The OVS
∗
and UVS
∗
measure a phase-to-phase voltage while the OVG
∗
and UVG
∗
measure a
phase-to-earth voltage. These detectors are used for overvoltage and undervoltage protection as
described in Section 2.4.9.
Residual overvoltage detector OVG
This detector measures a residual voltage and its sensitivity is fixed at 20V. This detector is used
for supervision of VT failure.
Undervoltage detector UVLS and UVLG
The UVLS measures a phase-to-phase voltage while the UVLG measures a phase-to-earth
voltage. Their sensitivity can be set. These detectors are used for weak infeed tripping.
Undervoltage detector UVFS and UVFG
The UVFS measures a phase-to-phase voltage while the UVFG measures a phase-to-earth voltage.
Their sensitivity can be set. These detectors are commonly used for the VT failure supervision and
signal channel test.
Undervoltage detector UVPWI
The UVPWI measures a phase-to-earth voltage and its sensitivity is 30V fixed. The UVPWI is
used for countermeasures for overreaching of a leading-phase distance element at positive phase
weak infeed condition.
Broken conductor detector BCD
The BCD measures the ratio of negative to positive phase sequence currents (I
2F
/ I
1F
).
Overcurrent detector OCBF
This detector measures A, B, and C phase currents and its sensitivity can be set. This detector is
used for breaker failure protection and resets when the current falls below 80% of the operating
value.
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......